Laserfiche WebLink
OIL EQUIPMENT SERVICE 5'r%TE LICE; NE:No.323417 <br /> ClAg<IF11'ATION: A 11A7.., C6I1)40 <br /> Division of Keith A. Tnlliu, 1110. S ATE E:NVIR INMI N'I'AL AS.NE:NSOR N, 111781 <br /> Telephone: (209)754-1808 <br /> Fax: (209)754-5726 <br /> LEAK DETECTOR TEST RECORD po t office Box 950 <br /> 750 Industrial Way <br /> SAN ANDREAS.CA IFORMA,95249 <br /> Customer Date <br /> Bob Cat Central 4/9/01 <br /> Location <br /> 1113 Shaw Rd. , Stockton, CA 95205 _ <br /> Technician Product <br /> James P. Hesketh Diesel <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> Tokheim 3/4hp. Can not read <br /> Leak Detector Identification <br /> Manufacturer Description (W), I Stplr Leak_I)clecli 1 <br /> Campo Miller Diaphragm-type— Electronic <br /> Piston-type LS 300 Plus <br /> Tamper-proof seal installed? Yes No R <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> I. Operating Pump Pressure 28 psi (para. 15) <br /> 2. Gallons per hour rate 3 (para. 22) <br /> 3. Line pressure with pump shut off 23 .psi (para. 23) <br /> 4. Bieedback Test with pump off N/A ml (para.26) <br /> 5. Step-through time to full flow N/p`_—__seconds (para. 30) <br /> 6. Leak detector stays in leak search posiliun (para. 42) Yes N/A <br /> N0 NTA <br /> LEAK DETECTOR TEST *Complete thermal expansion test <br /> Note: Pau Leak detector fustest protocol before failing leak detectox . <br /> Pail=teak detector fails lest protocol - <br /> Pass— <br /> — <br /> Fail_..X___— Does not go into alarm. <br /> 4/9/01 <br /> Technician Da t e <br /> JgAes P. Hesketh <br />