SWRCB, January 2002 Page of <br />9. FILL. RISER CONTAINMENT SUMP TESTING F� 9017 <br />Facility is Not Equipped With Fill Riser Containment Sums C <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br />Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />'I Other (Specify) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Fill Sump #1-91 Fill Sum #2-87 <br />Sum Diameter: 42" 42" <br />Equipment Resolution: .002 <br />Fill Sump # Fill Sump # <br />Sum De the <br />47" <br />50 %d' <br />Height from Tank Top to Top of <br />Hi hest Pi in Penetration: <br />14" <br />13 %" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />21" <br />20 %:" <br />Condition of sump prior to <br />testing: <br />Dry <br />Dry <br />Portion of Sump Tested <br />Water Level 23" <br />Water Level 22 VT <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Wait time between applying <br />water and starting test: <br />5 Minutes <br />5 Minutes <br />Test Start Time: <br />8:47 <br />8:52 <br />Initial Reading (R,): <br />.001 <br />.001 <br />Test End Time: <br />9:17 <br />9:22 <br />Final Reading (RF): <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />Change in Reading RF -R,: <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30Minutes <br />.005/30Minutes <br />Test Result: <br />Pass <br />Pass <br />Is there a sensor in the sump? <br />Yes <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Yes <br />Yes <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Yes <br />Comments — (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />Fill Riser Sump #1 is for Tank #2 Premium Unleaded. <br />Fill Riser Sump #2 is for Tank #3 Regular Unleaded. <br />Tank #1 Diesel, not equipped with Fill Riser Sump! <br />