Laserfiche WebLink
San Joaquin County <br />Environmental Health Department <br />t Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone:) 468-3420 Fax: (209) 468-3433 Web: www.sigov ora/ehd <br />[Z:ZUnderground <br />Storage Tank Program Inspection Report <br />Facility Name: <br />ORLANDOS <br />Facility Address: <br />18754 E HWY 26, LINDEN <br />Date: <br />July 11, 2017 <br />On Site Records <br />204 <br />CCR 2712(1) <br />Current monitoring plan approved by the EHD not found on site V R COS <br />205 <br />CCR 2712(i) <br />Failure to have an approved UST response plan available onsite V ❑ R o COS <br />206 <br />CCR 2712 <br />Failure to comply with UST operating permit conditions V ❑ R o COS <br />207 <br />HSC 25294 <br />Failed to record unauthorized release from primary containment V ❑ R o COS <br />208 <br />CCR 2650(e) <br />Failed to notify the EHD of a reportable unauthorized release D V ❑ R o COS <br />209 <br />CCR 2715(c) <br />Designated operator did not inspect all required items and/or the inspection reports not completed D V n R ❑ COS <br />210 <br />CCR 2715(e) <br />Designated operator monthly inspection reports not maintained on site for at least 12 months V ❑ R ❑ COS <br />211 <br />CCR 2715(f) <br />Designated operator employee training not performed or log not kept V ❑ R ❑ COS <br />212 <br />CCR 2715(f)(2) <br />Unstaffed facility failed to have or implement a training program approved by the EHD V ❑ R ❑ COS <br />213 <br />HSC 25281.5(b)(2) <br />Unburied fuel piping at marinas not visually inspected at feast daily or log not kept V o R n COS <br />214 <br />HSC 25281.5(b)(3) <br />Unburied emergency generator fuel piping not visually inspected at least monthly or log kept V iiR _.. COS <br />UST System Observations <br />301 <br />HSC 25292.1 <br />UST system is not operated to prevent unauthorized release, including spills and overfills <br />i V R u COS <br />302 <br />HSC 25291(b) <br />UST system incapable of detecting leak from primary into secondary containment (pre-Jul 2003) <br />j V ❑ R ❑ COS <br />303 <br />HSC 25290.2(d) <br />Monitoring system not maintained to detect entry into secondary containment (Jul 2003-Jun 2004) <br />D V ❑ R ❑ COS <br />304 <br />HSC 25290.1(d) <br />Monitoring system not maintained to detect entry into secondary containment (after Jul 2004) <br />j V ❑ R ❑ COS <br />305 <br />HSC 25290.1(a) <br />VPH monitoring of the interstitial spaces of the UST system is not maintained <br />D V ❑ R ❑ COS <br />306 <br />CCR 2630(d) <br />Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity <br />nV ❑ R ❑ COS <br />307 <br />CCR 2632(c) <br />Monitoring system of the interstitial space of a double walled system not maintained <br />V o R ❑ COS <br />308 <br />CCR 2636(f) <br />Failed to maintain a continuous monitoring system that activates an audible and visual alarm <br />V ❑ R ❑ COS <br />309 <br />CCR 2636(0(1) <br />Monitoring in sump / UDC failed to activate an audible and visual alarm or stop the Flow product <br />V ❑ R ❑ COS <br />310 <br />CCR 2636(f)(5) <br />Failure to meet monitoring requirements in lieu of annual line tightness test <br />n V ❑ R ❑ COS <br />311 <br />CCR 2638(x), 2641 Q) <br />Failed to property program or operate leak detection equipment <br />D V ❑ R n COS <br />312 <br />CCR 2638(f) <br />Failed to affix a tag sticker on monitoring equipment certified, repaired, or replaced <br />D V ❑ R ❑ COS <br />313 <br />HSC 25290.1, 25290.2, <br />25291 <br />Failure to construct, operate, and maintain primary containment as product-tight <br />j V o R o COS <br />314 <br />HSC 25290.1, 25290.2, <br />25291 <br />Failed to have secondary containment or secondary containment not tight <br />3 V o R ❑ COS <br />315 <br />HSC 25291(a) <br />Water in secondary containment not removed, analyzed, and properly disposed of (pre-Jul 2003) <br />3V ❑ R ❑ COS <br />316 <br />HSC 25290.1(c3), <br />25290.2(c3) <br />Secondary containment not constructed to prevent water intrusion (after Jul 2003) <br />o V o R ❑ COS <br />317 <br />CCR 2636(f)(2) <br />Line leak detector not installed <br />7 V ❑ R o COS <br />318 j <br />CCR 2636(f)(2) <br />Leak detector failed to detect a 3.0 gph leak at 10 psi <br />nV a R ■ COS <br />319 <br />CCR 2635(b) <br />No spill bucket, failed to contain five gallons, or failed to provide a means to keep it empty <br />3V ❑ R ❑ COS <br />320 <br />CCR 2635(b)(2) <br />Overfill prevention system not present or failed to meet overfill requirements <br />o V ❑ R ❑ COS <br />321 <br />CCR 2635(b)(2) <br />Overfill prevention was overridden <br />nV ❑ R ❑ COS <br />Page 2 of 4 <br />