SWRCB,January 2002 Page 2 <br /> 104. TANK ANNULAR TESTING <br /> Test Method Developed By: F-1 Tank Manufacturer ❑x Industry Standard Professional Engineer <br /> 0 Other (Specify) <br /> Test Method Used: F-1 Pressure Vacuum El Hydrostatic <br /> Other (Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank# 2 PLU Tank# 1 PRE Tank# 3 UNL Tank# <br /> Is Tank Exempt From Testing?1 Yes E No Yes El No Yes X No Yes No <br /> Tank Capacity: 10, 000 10, 000 10,000 <br /> Tank Material: DW FIBERG DW FIBERG DW FIBERG <br /> Tank Manufacturer: unknown unknown unknown <br /> Product Stored: PLUS PREMIUM UNLEADED <br /> Wait time between applying <br /> pressure/vacuum/water and 5min 5min 5min <br /> starting test: <br /> Test Start Time: 9:04 9:39 9:42 <br /> Initial Reading(RI ): 10hg 10hg 10hg <br /> Test End Time: 10 :04 10:39 10 :42 <br /> Final Reading(RF ): 10hg 10hg 10hg <br /> Test Duration: 1hr 1hr 1hr <br /> Change in Reading(RF-14 ): 0 0 0 <br /> Pass/Fail Threshold or Criteria: 2 hg 2 hg 2 hg <br /> Test Result: �Pass El Fail Pass El Fail E Pass El Fail 1:1 Pass El Fail <br /> Was sensor removed for testing? YesMN NA❑YesEN NA❑Yes x N NA❑YesE:]No❑NA <br /> Was sensor properly replaced and Pet"-iNcONA� ❑Ye F---1 ❑Ye�Nc�NA E]Yes�NCNA <br /> verified functional after testing? <br /> Comments - (include information on repairs made vrior to testing, and recommended follow-up for failed tests) <br /> t Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />