Laserfiche WebLink
� a LDT 5000 Field Test Apparatus <br /> 431op ■animolOgy Line Leak Detector Test Page 1 of 1 <br /> Work Order: 2309197 Date: 2/25/2013 <br /> Site Name/ID: CHEVRON#98264(N-534)/98264 <br /> Address: 3775 N.TRACY BLVD <br /> City: TRACY State: CA Zip: 95376 <br /> rank ID T1 T2 T3 <br /> roduct SUPREME PLUS REGULAR <br /> roduct Line 1 1 1 <br /> rested From 1 1 1 <br /> xisting/New Existing Existing Existing <br /> echanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLL <br /> Serial No. 242496 180356 06492 <br /> ump Operating Pressure(psi) 31.00 33.00 29.00 <br /> alibrated Leak(ml/min) 189.0 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 3.00 <br /> olding PSI <br /> NIA for Electronic Lo's <br /> esiliency(ml) <br /> N/A for Electronic Lo's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> pening Time(sec) <br /> N/A for Electronic LD's <br /> est Results Pass Pass Pass <br /> Technician Comments: Replaced 87 Preset chk valve, Passed after repairs. <br /> Technician Name: Ryan Casey Certification#: 96437 <br /> Technician Signature: Expire Date: 11/12/2015 <br /> Environmental Compliance for Petroleum Systems <br /> ®2013Tenlmdogy Inc..Aubn,Tx. AlingMsreserve0. terkrwW .rn <br />