Laserfiche WebLink
SPILL/OVERFILL CONTAINMENT BOXES Page 1 of 1 <br /> RTestMegPMPPVacut_m <br /> ped With Fill Riser Containment Sumps r <br /> ent Sumps are Present, but were Not Tested r <br /> oped By: r' Spill Bucket Manufacturerr Industry Standard f Professional Engineer <br /> r' Other (Specify): <br /> thod Used By: C Pressure r Vacuum C: Hydrostatic <br /> �" Other (Specify): <br /> Test Equipment Used: [MAKE TEST; Equipment Resolution: 0_062525 n. <br /> Spill Box # Spill Box # Spill Box # <br /> Tank TI SUPREME Tank T2 PLUS Tank T3 REGULAR Spill Box # <br /> Fill - Direct Fill - Direct Fill - Dlrect <br /> Bucket Diameter: 13.00 13.00 <br /> 13.00 <br /> Bucket Depth: 12.00 12.00 12.00 <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min 10 min <br /> starting test 30 Tin min <br /> Test Start Time: 08:00:00 08:00:00 09:30:00 <br /> Initial Reading q,: 9.50 in. 9.50 in. 9.00 in. <br /> Test End Time: 09:00:00 09:00:00 10:30:00 <br /> Final Reading am 9.50 in. 9.50 in. 9.00 in. <br /> Test Duration: 1 hr 1 hr 1 hr <br /> Change in Reading rv.5i: 0.00 in. 0.00 In. 0.00 in. <br /> Pass/Fail Threshold or criteria: +/- 0.00 +/- 0.00 +/- 0.00 <br /> Test Result: PassPass Pass <br /> Comments ? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> j CLEAN DRAIN VALVE ON REG SPILL BUCKET AND RE-TEST HYDROSTATIC.ALL SPILL BUCKETS PASS. <br /> i <br /> I <br /> i <br /> WO: 2301764 <br />