Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sums ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(SpeciA) <br /> Test Equipment Used: Caldwell Level Chan,geIndicator Equipment Resolution: .002 <br /> Fill Sump#1-Diesel Fill Sump# Fill Sump# Fill Sump# <br /> Sump Diameter: 48" <br /> Sump Depth: 65" <br /> Height from Tank Top to Top of 26" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 30" <br /> Electrical Penetration: <br /> Condition of sump prior to Dry DEC 1 9 2017 <br /> testing: <br /> Portion of Sump Tested Water Level 28" <br /> Sump Material: Fiberglass AL <br /> REAUff- <br /> Wait time between applying 5 MinutesT <br /> water and startingtest: nEP PTMEN <br /> Test Start Time: 1:48 <br /> Initial Reading (R,): .001 <br /> Test End Time: 2:05 <br /> Final Reading(RF): > .030 <br /> Test Duration: 15 Minutes <br /> Chane in Reading RF-Rt): > .030 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes <br /> Test Result: Fail <br /> Is there a sensor in the sump? Yes <br /> Does the sensor alarm when <br /> either product or water is Yes <br /> detected? <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up forfailed rests) <br /> Diesel Fill Riser Sump will not maintain test level and has a gross loss>.030 in 15 Minutes. <br /> I reset the Level Change indicator three times to verify a consistent loss. <br /> No visual signs of bubbles around Vapor/Vent Piping or Vapor/Vent Piping Penetrations. <br /> All Piping and Electrical Penetration in this Sump are Blue Line Material. <br /> No visual signs of penetration material degradation at time of this testing. <br /> Unable to locate source of loss. <br /> Recommend a repair contractor reseal all Piping and Electrical Penetrations in this Fill Riser Sump. <br /> Retest after repairs. <br />