Laserfiche WebLink
ITTS Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> 'ZEST RESULTS <br /> March 11 , 1989 <br /> City of Tracy <br /> Attn: Don Mason <br /> 560 Tracy Boulevard Site : Boyd Service Center <br /> Tracy, California 95376 560 S . Tracy Blvd . <br /> Dear Mr . Mason : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to' the appropriate governmental <br /> agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the loss or gain is less than . 05 gallons per one hour <br /> of testing . If the results are beyond these parameters , you <br /> should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 4, 000 Diesel - . 003 Yes <br /> Center 8, 000 Reg U/L - . 040 Yes <br /> West 8, 000 Prem U/L - . 035 Yes <br /> Please contact us if you need addi.tional assistance or <br /> information. <br /> Sincerely, <br /> - W. Savage _ <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />