ITTSIntegrity Tek Testing Systems, Inca <br /> TEST DATA AND <br /> TEST RESULTS <br /> June 30, 1988 <br /> .Jim Martin <br /> GENERAL MILLS , INC . <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr . Martin: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing . If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #( TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12, 000 #5 Diesel - . 00704 Yes <br /> Center 12 , 000 #5 Diesel - . 01469 Yes <br /> West 12, 000 #5 Diesel - . 03034 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> Frank Keser <br /> Certified T er <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036,1 <br />