Laserfiche WebLink
Amk <br /> Integrity Tank Testing Systems, Inc. <br /> ITTS <br /> TEST DATA AND <br /> TEST RESULTS <br /> April 25, 1988 <br /> Jim Martin <br /> GENERAL MILLS, INC. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr. Martin: <br /> tollo,;ing is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental ngeucy. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 0: <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial ectivu. <br /> TANK 111' TANK PRODUCT TEST WITHIN TIG117 <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAIIETnR° <br /> East 12, 000 #5 Diesel - . 03508 Yes <br /> Center 12, 000 #5 Diesel -. 00764 Yes <br /> West 12, 000 #5 Diesel -. 0077 Yes <br /> Please contact us if you need additional assistance or <br /> ur.mation, <br /> SLocern_ly , <br /> grain , Keser <br /> Certified Te ter <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />