Laserfiche WebLink
ITISIntegrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> March 21 , 1988 <br /> Mr. Jim Martin <br /> General Mills , Inc. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr. Martin: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> :Inclosed are copies of the tent worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 05 <br /> ga.11.ous per one hour of testing. If the results are beyond these <br /> par.nmeta-s , you should consider taking some remedial action . <br /> °ANK #/ TANK PRODUCT TEST WITHIN TI011T <br /> LOCA.FIi1N CAPACITY CONTAINED RESULTS TANK FARAMFTERS <br /> East 12, 000 #5 Diesel -. 00902 <br /> Center 12, 000 #5 Diesel +. 00796 Yes <br /> Yes <br /> West 12,000 #5 Diesel -. 00008 <br /> Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> ' Sincere <br /> , <br /> ra �� <br /> Frank Keser <br /> '-e- ratified Tet <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />