Laserfiche WebLink
IT T S integrity Took Testing Systems, Inc. <br /> TEST ll ATA AND <br /> TFST RES(TLTS <br /> January 28, 1988 <br /> Mr. Jim Martin <br /> GENERAL MILLS , INC. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr. Martin : <br /> 7oflowing is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s ) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> TANK ll/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12 ,000 X15 Diesel +, 01416 Yes <br /> Center 12,000 #5 Diesel +, 00413 Yes <br /> West 12 ,000 #5 Diesel -. 0246 Yes <br /> Please contact us if you need additional assista�ice cr <br /> information . <br /> Sic:cerely , <br /> r <br /> Frank K se <br /> 1.9 rtifl.- ester <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />