Laserfiche WebLink
Integrity Tek Testing Systems, Ina <br /> I T T S <br /> TEST DATA AND <br /> TEST RESULTS <br /> November, 30 , 1987 <br /> - Mr. Jim Martin <br /> GENERAL MILLS , INC. <br /> 2000 V. Turner Road <br /> Lodi, California 95240 <br /> 'Dear Mr. Martin : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental ageucy . <br /> A tank system is considered tight , according to the current: <br /> rn '•.ev , if the gain is less than .02 or the loss is less than . 05 <br /> ^,'11].0119 per one hour of testing. If the results are beyond these <br /> parameters, - you should consider taking some remedial action. <br /> TA;.Y. R/ TANK PRODUCT TEST WITHIN TTG11"I' <br /> LI Oi_TI.ON CAPACITY CONTA111ED RESULTS TANK PARAME'rFRS <br /> West 12 , 000 #5 Diesel -, 04013 Yes <br /> Center 12 , 000 #5 Diesel <br /> Manifolded <br /> East 12 ,000 #5 Diesel -. 02803 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> \::6Ke4, ' <br /> Certified ter <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />