Laserfiche WebLink
iT T S Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> August 31 , 1987 <br /> Mr. James Martin <br /> General Mills , Inc. <br /> 2000 West Turner Road <br /> Lodi, California 94240 <br /> Dear Mr. Martin : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> TANK (1/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12 ,000 #5 Diesel +. 00702 Yes <br /> Center 12 ,000 #5 Diesel -. 0224 Yes <br /> West 12 , 000 #5 Diesel -. 01042 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> Frank Ke er <br /> Certifie T ter <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />