Laserfiche WebLink
IT I S Integrity Tank Testing Systems, Inc. j <br /> TEST DATA AND <br /> TEST RESULTS <br /> July 27 , 1987 <br /> General Mills , Inc. <br /> Attn: James Martin <br /> 2000 West Turner Road <br /> Lodi, 'California 95240 <br /> .Dear Mr. Martin : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the Lest worksheets and graphs gene- <br /> Lated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules, if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAIIETERS <br /> East 12 ,000 #5 Diesel +. 00066 Yes <br /> Center 12 ,000 #5 Diesel -. 01176 Yes <br /> West 12 ,000 #5 Diesel -. 0378 Yes <br /> Please contact us if ;you need additLonal assistance or <br /> information. <br /> Sincerely, <br /> Aak Keser <br /> Certified Te er <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />