IMF- <br /> I T T S Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> June 30 , 1987 <br /> GENERAL MILLS , INC. <br /> Attn: Jim Martin <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr. Martin: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank- system is considered t:i3ht , according to the current <br /> rules , if the gain is less than . 02 or the less is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial. action. <br /> TANK #/ TANK PRODUCT TEST WITHIN 't i.(:}I'r <br /> LOCATION CAPACITY CONTAINI;111 RESULTS TANK PARr�NE.TERS <br /> East 12 ,000 X15 Diesel +. 01328 Yes <br /> Center 12 , 000 #5 Diesel -. 0096 Yes <br /> West 12 ,000 #5 Diesel -. 01432 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> 'Sincerely, <br /> Frank ese <br /> Certifi d ester <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />