Laserfiche WebLink
c _ , <br /> =T T s Integrity Took Testing Systems, Inc <br /> 1411h 11 15r. 11 <br /> OCT 1 1 1988 <br /> ENVEALTH <br /> PERN I SERVICE' ] <br /> TEST DATA AND <br /> TEST RESULTS <br /> December 12 , 1987 <br /> GENERAL MILLS , INC. <br /> 2000 West Turner Road <br /> Lodi , California 95240 <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Northwest 500 Diesel Fuel -. 0014 Yes <br /> of office <br /> Please contact us if you need additional assistance or <br /> inf rmatiun. <br /> Sincerely , <br /> W. Savage <br /> C=_rtified Tester <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />