i <br /> IT T S Integrity Tek Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 12 , 1988 <br /> GENERAL MILLS , INC. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> RE: CO-GENERATION PLANT <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> riles , if the gain is less than. . 02 or the ions is less than .05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK ll/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East <br /> Test #1 10,000 Kerosene -.42786 No <br /> Test #2 10 ,000 Kerosene -. 421088 No <br /> r REFER TO COVER LETTER. <br /> Please contact us if you need additional assistance or <br /> j.ofovmation. <br /> Sincerely , <br /> W. Savage <br /> Certified Taster <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />