Laserfiche WebLink
ITISIntegrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 12 , 1988 <br /> GENERAL MILLS , INC. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> RE : CO-GENERATION PLANT <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s ) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated fnr your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing . If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East Tank 10 ,000 Kerosene -. 044192 ** <br /> **THIS IS A TANK ONLY TEST. <br /> REFER TO COVER LETTER. <br /> r <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> /j,y''C4u <br /> W. Savage <br /> Certified Tester <br /> 800 262 TEST 166 Fronk West Circle Stockton, CA 95206 (209) 466-8032 <br />