Laserfiche WebLink
Integrity Tank Testing Systems, Inc. <br /> ITT <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 12 , 1988 <br /> GENERAL MILLS, INC, <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> RE: CO-GENERATION PLANT <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(e ) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight, according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ 'TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARA14ETERS <br /> East Tank 10 ,000 Kerosene -.044192 ** <br /> **THIS IS A TANK ONLY TEST. <br /> REFER TO COVER LETTER. <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> W. Savage <br /> CArtified Tester <br /> 800 262 TEST 166 Frank West Circle _ Stockton, CA 95206 (209) 466-8036 <br />