Laserfiche WebLink
ITTS ; <br /> Integrity Tank Testing Systems, Inc. <br /> August 29, 1988 <br /> TEST DATA & RESULTS <br /> GENERAL MILLS, INC. <br /> 2000 West Turner Road <br /> Lodi, CaZifornia 95240 <br /> The following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and graphs generated <br /> during the testing. They are provided for your submittal to the <br /> appropriate govenmental agency. <br /> A tank system is considered tight, according to the current <br /> regulations, if the gain is less than .02 or the loss is less than .05 <br /> gallons per one hour of testing. If the results shown below are <br /> beyond these parameters, you will need to take remedial action. <br /> Please note page 2 of this letter if a no is shown in the final column <br /> below. <br /> TANK # / TANK PRODUCT TEST WITHIN "TIGHT" <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Center 12, 000 #.5 DieseZ -. 02816 Inconclusive <br /> Please contact us if you need - additional assistance or <br /> information. <br /> Sincerely, <br /> i <br /> Frank Xeser <br /> Certified Te ter <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 s' <br />