$TTS Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> July 21, 1988 <br /> Jim Martin <br /> General Mills, Inc. <br /> 2000 West Turner Road <br /> Lodi, California 95240 <br /> Dear Mr. Martin: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12, 000 #5 Diesel -. 02184 Yes <br /> Center 12, 000 #5 Diesel +. 01629 Yes <br /> West 12, 000 #5 Diesel -. 04096 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> sincerely, <br /> iank Keser <br /> ,ertified Te er <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />