Laserfiche WebLink
ITISIntegrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> March 24 , 1988 <br /> ROBERTS PETROLEUM SERVICES , INC. jVj930 Victor Road <br /> Lodi, California 95240 APR 14 1988 <br /> ENVIROMENTAL HEALTH <br /> FERMIT/SERVICES <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> ramie:; , if the gain is less than .02 or the. loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> 2nd South 10,000 Kerosene -. 04081 Yes <br /> North 10,000 Diesel -. 01365 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> flank Kese <br /> Certified fe�se'r <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 966-8036 <br />