Laserfiche WebLink
CGRS REGFV,, 1VED <br /> 0 SOLUTIONS DELIVERED ll I 2017 <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICE�M" SH 'T <br /> PRESSURIZED <br /> Date: 03/20/17 Work Order# 9237 <br /> Location: Valley Pacific Contact: Mike Eliason <br /> 930 E. Victor Rd. <br /> Lodi, Ca.95240 Telephone: (209)993-8793 <br /> SUMP# #1-2 #1-2 <br /> PRODUCT T-6 87 T-787 <br /> LD TYPE Mechanical, (W)PLLD, (P)LLD I M M <br /> LD MANUFACTURER VMI VMI <br /> LD MODEL LD-2000 LD-2000 <br /> LD SERIAL NUMBER 15021137 07031410 <br /> SUMP CONDITION Dry Dry <br /> RESILIENCY 150ML 110ML <br /> OPERATING PRESSURE 24 PSI 25 PSI <br /> OPENING TIME 4 seconds 6 seconds <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 18 PSI 18 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? Yes Yes <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A NIA <br /> LD PASS OR FAIL? Pass Pass <br /> Comments: <br /> Technician: RICHARD THOMAS Contractor Lic. # 803616 <br /> Signature: �� <br />