Laserfiche WebLink
IF <br /> SWRCB,January 2002 • Page 2 <br /> IF . <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes: <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested: <br /> Test Method Developed By: Spill Bucket Manufacturer EK1 Industry Standard ElProfessional Engineer <br /> Other(Specify) <br /> Test Method Used: ❑ Pressure ❑ Vacuum ❑X Hydrostatic <br /> F] Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> " Spill Box# 1-87 Spill Box# 2-89 Spill Box# 3-91 Spill Box# <br /> Bucket Diameter: 10 1/2 10 1/2 10 1/2 <br /> Bucket Depth: 16 16 16 <br /> Wait time between applying <br /> pressure/vacuum/water and SMIN. SMIN. SMIN. <br /> starting test: <br /> Test Start Time: 8:50 8:50 8:50 <br /> Initial Reading(RI ): 9" 9" 9" <br /> Test End Time: 9:55 9:55 9:55 <br /> Final Reading(RF ): 9., 9" 9" <br /> Test Duration: 6OMIN. 60MIN. 60MIN. <br /> Change in Readin (RF-Rt ) 0" 0" 0" <br /> Pass/Fail Threshold or PASS PASS PASS <br /> Criteria: <br /> Test Result: E Pass 1:1 Fail I % Pass 0 Fail I [K]Pass ❑ Fail 1 ❑Pass Fail <br /> Comments- (include information on repairs made prior to testing, and recommendedfollow-upforfailed tests) <br /> OPW SPILL BUCKETS ON SITE. <br />