Laserfiche WebLink
ITT S Integrity Took Testing Systems, Inc. <br /> TEST DATA AND <br /> *OP v� TEST RESULTS <br /> October 27 , 1987 <br /> Mr. John Hatton <br /> My Mini Mart <br /> 1756 N.. Wilson Way <br /> Stockton , California 95205 <br /> Dear John : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the teat worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight, according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK O/ TANK PRODUCT TEST WITHIN TIGU'r <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 10 ,000 Reg. Gaso . -. 0228 Yes <br /> West 10 ,000 U/L Gaso. -. 0433 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> Frank Kes r <br /> Certified ester <br /> 800 262 TEST 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />