Laserfiche WebLink
SECTION 6 ♦ Installation <br /> -'RLE 1.6.2 Adhesive Kit Data <br /> .7000 Series <br /> • For Petroleum Products in all Piping Systems <br /> • For Petroleum Products,Alcohols,and Alcohol-Gasoline Mixtures in Secondary Containment Systems <br /> Approximate No.of Bonds per Kit Working <br /> 2" 3" 4" Life(') <br /> Kit(2) Quantity Mixed Adhesive (50 mm) (75 mm) (100 mm) (Min.) <br /> DS-7014 6.8 oz. (193 g) 25 18 10 25 <br /> DS-7024(twin pack) 2.5 oz. ea. (71 g ea.) 18 10 6 25 <br /> DS-7069(3) 9.95 oz. (282 g) - - - 25 <br /> DS-8000 Series <br /> • For Use with RED THREAD IIA Pipe and Fittings or RED THREAD IIA Secondary Containment Fittings <br /> for Petroleum Products,Alcohols, and Alcohol-Gasoline Mixtures <br /> Approximate No.of Bonds per Kit Working <br /> 2" 3" 4" Life(') <br /> Kit(2) Quantity Mixed Adhesive (50 mm) (75 mm) (100 mm) (Min.) <br /> DS-8014 6.4 oz.(181 g) 21 15 8 15 <br /> DS-8024(twin pack) 2.7 oz.ea.(77 g ea.) 18 12 7 15 <br /> DS-8055(bag kit) 1.6 oz. (45 g) 6 4 2 15 <br /> DS-8069(3) 9.3 oz. (264 g) - - - 15 <br /> (1)working life Is the time It takes a properly (2)Solvent does not come with the adhesive kits; (3)Not recommended for 2'.3',and 4'(50 mm. <br /> .can of adhesive to"set up'at 75'F. It must be ordered separately. 75 mm,and 100 mm)Installations because of the <br /> Ar of bonds is based on the volume in the large quantity of adhesive per kit. <br /> kit and must be completed within the working <br /> life of the kit. <br /> Note: Using solvent as a cleaning method is optional. <br /> �- 3•� y if preferred by the customer,use solvent. 1,1,1 <br /> trichloroethane solvent is available from Smith <br /> Fiberglass Products. Some alternate cleaning solvents <br /> available through local hardware or industrial supply <br /> houses are acetone, alcohol, methylene chloride, and <br /> 3 - i methyl ethyl ketone. After cleaning, be sure any resid- <br /> ual solvent <br /> esid- <br /> ualsolvent has evaporated before applying adhesive. <br /> DO NOT USE SOLVENTS THAT LEAVE AN OILY <br /> ` a FILM ON THE BONDING SURFACES. <br /> a.} '1'Hc-E WARNING: <br /> 7r i., "' '`a,.� k:r:' + h: Some de- <br /> zi,�£''' `r . ° i5a"f'xFleune 16.4 greasers and <br /> solvents are <br /> extremely <br /> • Cut off contaminated surface and replace with a new flammable. <br /> taper or sleeve coupling. Be sure to read <br /> warning labels <br /> • Wire bushes may be used for cleaning T.A.B.surfaces; on containers. <br /> however, they must be clean and free of oily contami- Never use <br /> ition. gasoline, tur- <br /> pentine, or <br /> • Dirt contamination can be removed by water washing. diesel fuel to <br /> Be sure the surfaces are dry before bonding. clean joints. FIGURE 1.6.5 <br /> 10 Installation Instructions <br />