Laserfiche WebLink
SWRCB,January 2002 Page_of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer D Industry Standard D Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure X Vacuum D Hydrostatic <br /> D Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution:-%:"x-301-1g. <br /> Tank#1,2&3 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' 11 Yes x No D Yes O No D Yes D No D Yes D No <br /> Tank Capacity: 20K Split 10/5/5 <br /> Tank Material: Jacketed Steel <br /> Tank Manufacturer: Total Containment <br /> Product Stored: 87/87/Diesel <br /> Wait time between applying 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:40 <br /> Initial Reading(R,): -10 Hg. <br /> Test End Time: 12:40 <br /> Final Reading(RP): -10 Hg. <br /> Test Duration: 2 Hours <br /> Change in Reading(R,-R,): 0 Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. <br /> Test Result: X Pass [I Fail D Pass 0 Fail 11 Pass D Fail ❑ Pass 0 Fail <br /> Was sensor removed for testing? XYes -No _SNA Ll Yes L1 No DNA DYes ENO DNA OYes ONO DNA <br /> Was sensor properly replaced and XYes -No DNA ❑Yes El No DNA L]Yes DNo DNA ❑Yes 11No El NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommendedfollow-upforfailed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />