INVOICE #AT000137 TEST DATE: 05/12/95 <br /> AFFORDA-TE$T <br /> PO BOX 36 Rv%glyTHORNTON, C3 95686 <br /> ( 209)794-0102 or (800)524-9087 <br /> 21995 <br /> TANK STATUS EVALUATION REPORTJUN----------------------------- ENARONMENTALHA <br /> ***** CUSTOMER DATA ***** ***** SITE DATA I �4ERVICEEL711 <br /> S <br /> PANELLA TRUCKING PANELLA TRUCKING <br /> POB 5010 5000 E. FREMONT ST <br /> STOCKTON, CA. 95205 STOCKTON, CA. 95205 <br /> CONTACT: MARLING, TIM CONTACT: MARLING, TIM <br /> PHONE #: ( 209)943-5000 PHONE #: ( 209)943-5000 <br /> ***** COMMENT LINES ***** <br /> FOUR 12K DIESEL TANKS WITH TWO MAIN LINES. ONE NEW OIL. <br /> ONE 10K GAS WITH ONE SUCTION LINE. ONE EMPTY WASTE OIL. <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK #1: DIESEL FUEL 2 TYPE: STEEL RATE: .004570 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: .16 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: STEEL RATE: . 035051 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: .62 <br /> TANK IS TIGHT. <br /> TANK 13: DIESEL FUEL 2 TYPE: STEEL RATE: .022320 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.02 <br /> TANK IS TIGHT. <br /> TANK #4: DIESEL FUEL 2 TYPE: STEEL RATE: .022960 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: . 62 <br /> TANK IS TIGHT. <br /> TANK #5: PLUS UNLEADED TYPE: STEEL RATE: . 005240 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: . 24 <br /> TANK IS TIGHT. <br />