Laserfiche WebLink
F. SYSTEM PIPING CONTINUED: BCE#10050 <br /> Check Cod <br /> Box echo. <br /> ❑X 25290 .1 c 1 Piping compatible with material intended to be stored. <br /> 25290.2 c 1 <br /> 23 CCR <br /> ly� 2631(b) Design and construction of piping approved by independent testinorganization e. . UL). <br /> Ex Piping, including vent lines,sloped toward tank(s)with minimum 1/4 inch sloe per 1 foot of run. <br /> HSC )) <br /> 25290.1�k) j) Vapor recovery,fill riser, and vent line piping are secondarily contained. <br /> IN G. OVERSPILL/ OVERFILL PREVENTION: <br /> Check Code <br /> Box Section <br /> 23 CCR Overspill containment having minimum capacity of 5 gallons provided at each tank fill location. <br /> tX 2635(b) Manufacturer OPW Model <br /> Approved overfill prevention device provided at each tank fill location. <br /> Choose One of the following methods: <br /> X Alert the transfer operator when the tank is 90 percent full by restricting the flow into the tank or <br /> triggering an audible visual alarm <br /> ❑ Restrict delivery of flow to the tank at least 30 minutes before the tank overfills,provided the <br /> 23 CCR restriction occurs when the tank is filled to no more than 95 percent capacity; and activate an <br /> [X 2635(b)(2) audible alarm at least five minutes before the tank overfills <br /> ❑ Provide positive shut-off flow to the tank when the tank is filled to no more than 95 percent of <br /> capacity. <br /> ❑ Provide positive shut-off of flow to the tank so that none of the fittings located on the top of the <br /> tank are exposed to product due to overfilling. <br /> Manufacturer Veeder-Root Model Overfill Alarm#790091-002;with Level Gauge#846391-6 1 <br /> H. CORROSION PROTECTION: <br /> Check Code <br /> Box Section <br /> IX Fiberglass reinforced plastic(FRP) <br /> Piping corrosion protection: ❑ Steel with cathodic protection or impressed current <br /> �} 23 CCR ❑ Steel isolated from contactwith backfill <br /> 2636(b) <br /> CXFRP or equivalent non-metallic exterior coatings or coverings <br /> Tank corrosion protection: ❑ Sacrificial Anode <br /> �{ 23 CCR <br /> 2635(a)(2) 11Steel tank with field installed cathodic protection or impressed <br /> current <br /> Tie-downs,when used,constructed of non-corrosive material or coated steel. (Tar Coat Epoxy) <br /> Revised 8/1/11 7 <br />