Laserfiche WebLink
Enter type installation <br /> Enter Number of Tanks in Hole <br /> (value ignored for single tank installation) <br /> T _0 For Multiple Tanks _ <br /> Install 0 = side by side, NTanks -' <br /> 1 = end to end JAN 1 3 2018 <br /> ENVIROI WENT I HEALTH <br /> Enter solutions that will be evaluated in this sheetC"'n' `. <br /> hasdeadmen= I Set to 1 if sheet will include deadmen solution, 0 if not ���,-�. �i iti+EfVT <br /> DeadmenDesign =if(hasdeadmen,"A deadmen solution is provided" ,"No deadmen solution is provided") <br /> DeadmenDesign = "A deadmen solution is provided" <br /> hasanchorslab-0 Set to 1 if sheet will include anchor slab solution, 0 if not <br /> AnchorSlabDesign=if(hasanchorslab,"An anchor slab solution is provided" ,"No anchor slab solution is provided") <br /> AnchorSlabDesign = "No anchor slab solution is provided" <br /> Required Factory Safety against Float <br /> Fsfloat= 1.2 PEI RP100-11, Section A.9 - recommends a FSfloat of 1.2, <br /> OSHPD in California requires an FSfloat of 1.5 <br /> iCity Gas and Food-Lathrop CA-dwg 11313-002_8ft 12M_ver 2 60 10-17-16.xmcd Page 4 of 15 <br /> Date Printed: 2/7/2017 <br /> 1 <br />