Laserfiche WebLink
SAN10 A Q U I N Environmental Health Department <br /> C 0 U - 'r'' <br /> I. MONITORING: All monitoring equipment must be listed in the State Water Resources Control <br /> Board Division of Clean Water Program Local Guidance Letter 113. <br /> Check Code <br /> Box Section <br /> 23 CCR All secondary containment units (e.g. tank annular spaces, secondary piping, sumps, <br /> XX 2632 under-dispenser containment, etc.) monitored for leaks using approved electronic leak <br /> 2636(f) detections stems. <br /> Electronic monitoring sensors located at the following points: <br /> ° At the bottom of the interstitial space of each secondarily-contained tank, <br /> positioned as near as possible to the bottom of the tank. <br /> Manufacturer Veeder Root Model 794380-303 <br /> ° In each collection sump, positioned as near as possible to the bottom of the <br /> collection sump. Additionally, in any sump acting as secondary containment for <br /> unused tank openings which connect to the primary space. <br /> Manufacturer Veeder Root Model 794380-208 <br /> xx 23 CCR <br /> 1 2632 <br /> 2630(d) ° In dispenser pans which do not drain into secondary containment piping. <br /> (Note:A mechanical switch which triggers a shear valve may be substituted but <br /> this system will not qualify for the annual line tightness test exemption under 23 <br /> CCR 2636(g)). <br /> Manufacturer Veeder Root Model 794380-208 <br /> ❑Along secondarily-contained pipe runs which do not meet the 1/8 inch-per-foot <br /> slope requirement, positioned in the depressed or low-lying areas. <br /> Manufacturer Veeder Root Model 794380-208 <br /> 23 CCR Automatic line leak detectors installed to monitor underground pressurized piping. <br /> 2636(f) <br /> XX HSC Manufacturer Veeder Root Model 848480-001 <br /> 25290.1 h <br /> 25290.2 <br /> Alarm panel provides both audible and visual alarms. It is located in a protected area <br /> 23 CCR and within sight and hearing distance of on-site personnel and hard-wired to a <br /> 2632(c)(2)(B) dedicated circuit. <br /> Manufacturer Power Integrity Model 790091-001 & 790095-001 <br /> J. OTHER COMPONENT INFORMATION: <br /> COMPONENT MANUFACTURER MODEL COMPOSITION <br /> SUMP CSI DWPTS Fiberglass <br /> UNDER-DISPENSER Bravo B8000-F2L-BD-AB Fiberglass <br /> CONTAINMENT <br /> PENETRATIONS Bravo F-32-TS-D Fiberglass <br /> 8of8 f <br />