R"ECEIVED <br /> a 0 9 2019 <br /> CONTAINMENT EVViViEN TA <br /> S O L U T I O N S,P HEALTH DEPARTMENT <br /> Terry Masters January 7, 2019 <br /> Elite IV Construction <br /> Reference: City Food& Liquor 16470 Cambridge Dr., Lathrop, CA 95330 <br /> Pre-Installation Testing at 3psi for Tanks on Order 85479 <br /> Dear Mr. Masters, <br /> Containment Solutions installation instructions require a pre installation pressure test on the main tank <br /> when it is received on the jobsite to make sure there is no damage that has occurred in shipment or <br /> unloading of the tank.The standard pre installation air/soap test is performed at 5psi. If any suspect <br /> areas are found,they would be brushed with the soap and water solution to see if any bubbles develop. <br /> This letter certifies that even though the tank pre installation air/soap test was performed at 3psi <br /> instead of the required Spsi,the 3psi air/soap test is adequate for the 8'-12000&8'-6000/6000 DWT6 <br /> hydrostatic annular space tanks on the referenced project. The warranty will be in effect as originally <br /> provided by Containment Solutions at the time of the tank delivery. <br /> This variance is for the referenced installation only. All future tank installations should follow the <br /> guidelines published in the CSI installation Instructions Pub No. Inst 6001. <br /> Thank you for using Containment Solutions fiberglass underground storage tanks for your project. If you <br /> have additional questions about any of the information provided, please let me know. <br /> Sincerely yours, <br /> Kevin A. Soeder <br /> Technical Specialist <br /> Containment Solutions, Inc. <br /> 936-756-7731 <br /> ksoeder@csiproducts.com <br /> .� <br /> CORPORATE OFFICE•333 NORTH RIVERSHIRE DR•SUITE 190•CONROE,TEXAS 77304•TELEPHONE: (936)756-7731 •FAX: (936) <br /> 756-7766 <br /> VM W.CONTAINMENTSOLUTIONS.COM <br />