SWRCB, January 2002 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Page of <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ✓❑ Industry Standard ❑Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: El Pressure ❑ Vacuum ❑Hydrostatic <br />Q Other (Specify) Inches, 1 hr visual test <br />Test Equipment Used: See attached testing procedures Equipment Resolution: Imhae.l h,v 1n= <br />Spill Box # 87 Fill Spill Box # 87 Vapor Spill Box # 91 Fill Spill Box # 61 Vapor <br />Bucket Diameter: <br />12" <br />12" <br />12" <br />12" <br />Bucket Depth: <br />15" <br />15.5' <br />16" <br />15' <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 minutes <br />15 minutes <br />15 minutes <br />15 minutes <br />Test Start Time: <br />10:20am <br />10:20am <br />10:20am <br />10:20am <br />Initial Reading (Ri): <br />14.5 Inches, I h, visual less <br />15 Inches.I h --i -1 <br />15.5 Inches., hr visual test <br />15 Inchas.I h"Is-I <br />Test End Time: <br />11:20am <br />11:20am <br />11:20am <br />11:20am <br />Final Reading (RF): <br />14.5 Inches,, h, visual lust <br />15 Inch.,, I h, visual 1W <br />15.5 Inches., h,Nsuafes <br />15 hmahes.,h,viscaih <br />Test Duration: <br />1 Hr. <br />1 Hr. <br />1 Hr. <br />1 Hr. <br />Change in Reading (RF -R,): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Test Result: <br />✓❑Pass ❑Fail <br />OPass ❑Fail <br />❑Pass ❑Fail <br />✓❑Pass ❑Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up forfailed tests) <br />