PLUMBING LEGEND: PIPING: PIPING (continued): VALVES: GENERAL PLUMBING NOTES: <br /> INSTALLATION <br /> INSTALL EXPOSED PIPING FREE OF SAGS AND BENDSPROVIDE BRACKET STANDOFFS SCOPE <br /> . <br /> SOIL, WASTE, GREASE AND VENT PIPING GENERAL THE INTENT OF THE SPECIFICATION AND THE DRAWINGS IS TO PROVIDE A <br /> S OR W SANITARY OR WASTE PIPING ABOVE SLAB SOIL, WASTE AND VENT PIPING 10" AND SMALLER SHALL BE SERVICE WEIGHT, FROM MOUNTING SURFACES SUFFICIENT TO ALLOW 1" CLEANING SPACE AROUND ALL PLUMBING CONTRACTOR TO PROVIDE VALVES WHERE INDICATED ON PLANS AND COMPLETE AND FULLY OPERATIONAL PLUMBING SYSTEM. THE CONTRACTOR <br /> HUBLESS, CAST IRON PIPE AND FITTINGS WITH NEOPRENE GASKET AND STAINLESS PIPING, INCLUDING ANY ADDED PIPING INSULATION. INSTALL FITINGS FOR CHANGES IN AS NECESSARY FOR PROPER SYSTEM OPERATION AND COMPONENT ISOLATION. SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT RELATED TO THE <br /> S OR W SANITARY OR WASTE PIPING BELOW SLAB DIRECTION AND BRANCH CONNECTIONS. INSTALL SLEEVES FOR PIPES PASSING <br /> STEEL SHIELD AND CLAMP. PROVIDE HUB & SPIGOT, SERVICE WEIGHT CAST-IRON INSTALL VALVES FOR EACH FIXTURE AND REM OF EQUIPMENT. PROVIDE BRAIDED INSTALLATION OF THE PLUMBING WORK. <br /> SOIL PIPE AND FffTINGS BELOW GRADE WHERE REQUIRED BY LOCAL CODES. THROUGH CONCRETE AND MASONRY WALLS, GYPSUM BOARD PARTITIONS, CONCRETE STAINLESS STEEL HOSE (UNLESS OTHERWISE NOTED) BETWEEN VALVE AND <br /> - - - - SV SANITARY VENT PIPING SCHEDULE 40 ABS OR PVC PIPE AND FITTINGS WITH SOLVENT WELD MAY BE FLOOR AND ROOF SLABS. SEAL PIPE PENETRATIONS THROUGH RATED CONSTRUCTION EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. LOCATE SITE EXAMINATION <br /> SUBSTITUTED FOR SOIL, WASTE AND VENT PIPING ABOVE AND BELOW GRADE IF WITH FIRESTOPPING SEALANT MATERIAL UNDERGROUND WATER AND SEWER UNES SHUT-OFF VALVES ADJACENT TO EQUIPMENT FOR EASY ACCESS SUCH THAT THE CONTRACTOR SHALL THOROUGHLY EXAMINE ALL AREAS WHERE <br /> GW GW GREASE WASTE SHALL BE LAID IN SEPARATE TRENCHES WITH A MINIMUM HORIZONTAL SPACING AS <br /> ALLOWED LOCAL AUTHORITY. ALL HORIZONTAL RUNS SHALL DRAIN AT A GRADE VALVES CAN BE REACHED WITHOUT MOVING EQUIPMENT. FIXTURES, EQUIPMENT, AND PIPING WILL BE INSTALLED AND WILL REPORT ANY <br /> OF Y4" PERR FOOT REQUIRED BY CODE, EXCAVATED TO THE PROPER DEPTH AND GRADED TO PRODUCE CONDITION THAT, IN HIS OPINION, PREVENTS THE PROPER INSTALLATION OF THE <br /> CD CD CONDENSATE DRAIN COORDINATE WITH LOCAL AUTHORITIES FOR DRAINAGE REQUIREMENTS FOR THE REQUIRED FALL. VALVES PLUMBING WORK. Iflie <br /> CW COLD WATER PIPING EQUIPMENT DESIGNATED WITH INDIRECT WASTE TO FLOOR DRAINS. PROVIDE TESTING PROVIDE VALVES FOR WORKING PRESSURE IN WATER PIPING OF 125 PSI OR ®2017 STARBUCHS COFFEE COMPANY <br /> PIPED DRAIN TO SANITARY IF REQUIRED BY LOCAL JURISDICTION. ALL PIPES SHALL BE TESTED BY AN APPROVED METHOD BEFORE THEY ARE GREATER. UNLESS NOTED OTHERWISE VALVES SHALL BE AS FOLLOWS: STANDARDS <br /> BUILDING DRAIN AND VENT PIPING MATERIALS SHALL COMPLY WITH SECTIONS 701.0 BACKFILLED OR CONCEALED. AFTER TESTING IS COMPLEFE, THE PLUMBING EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE PROVISIONS OF <br /> HW HOT WATER PIPING CONTRACTOR SHALL DISINFECT THE POTABLE WATER SYSTEM AS REQUIRED BY VALVE TYPE MANUFACTURER MODEL NO. ASME, ASTM, UL, NEMA, ANSI, ASHRAE, NEPA, AS APPLICABLE TO EACH INDIVIDUAL STARBUCKS COFFEE <br /> AND 903.0 OF THE CALIFORNIA PLUMBING CODE, LOCAL AUTHORITY. TEST WATER PURITY ACCORDING TO LOCAL REQUIREMENTS CHECK VALVE (UP TO 2 NIBCO S-22 UNIT OR ASSEMBLY. <br /> -CWF- CWF COLD WATER FILTERED ALL SANITARY SYSTEM MATERIALS SHALL BE LISTED BY AN APPROVED LISTED AGENCY AND SUBMIT CERTIFIED TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL. FULL PORT BALL VALVE (UP TO 3") NIBCO S-FP-600 COMPANY <br /> GATE VALVE UP TO 3" NIBCO S-113 CODES 2401 UTAH AVENUE SOUTH <br /> CWN CWN COLD WATER NANO FILTERED I N S U LAT I 0 N . TEMPERATUREAND PRESSURE RELIEF VALVE WILKINS TP1100A ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH ALL APPUCABLE SEATTLE,WASHINGTON 98134 <br /> WATER HAMMER ARRESTOR WILKINS 1250 STATE AND LOCAL CODES AND ORDINANCES. IN CASE OF CONFLICT BETWEEN THE (206)318-1575 <br /> CITY NOTES: BACKFLOW PREVENTER WHOLE-HOUSE WILKINS 950XW DRAWINGS/SPECIFICATIONS AND THE CODES AND ORDINANCES, THE HIGHEST <br /> -CWS- CWS COLD WATER SOFTENED 1ALL ROOFTOP PIPING D(POSED TO WEATHER AND / OR SUNLIGHT WATER-PIPTRTBACKFLOW PREVENTER SINGLE DEVICE) WILKINS 700 STANDARD SHALL APPLY. THE CONTRACTOR SHALL SATISFY CODE THESE DRAWINGS AND SPECIFICATIONS ARE <br /> PROVIDE THERMAL INSULATION ON ALL HOT & COLD WATER, AND HORIZONTAL <br /> MUST BE METAWC. VACUUM RELIEF VALVE WILKINS 35VCH REQUIREMENTS AS A MINIMUM STANDARD WITHOUT ANY EXTRA COST TO CONFIDENTIAL AND SHALL REMAIN THE SOLE <br /> WASTE PIPING IN CEILING SPACES, PRESSURE REDUCING VALVE WILKINS 500YSBR <br /> TW TW TEMPERED WATER 2. ALL FERROUS PIPING EXPOSED 10 WEATHER SHALL BE GALVANIZED. AND ON ALL COLD WATER PIPING IN CASEWORK STARBUCKS. PROPERTY OF STARBUCKS CORPORATION, <br /> AND BAR AREAS. USE SELF-SEALING CLOSED CELL FOAM OR JACKETED FIBERGLASS TRAP SEAL PRIMER JAY R. SMITH 2699-1 WHICH IS THE OWNER OF THE COPYRIGHT IN <br /> INSULATION WITH MANUFACTURE APPROVED ADHESIVES, SEALERS, AND COATINGS. PERMITS AND FEES THIS WORK. THEY SHALL NOT BE <br /> RO RO REVERSE OSMOSIS WATER DOMESTIC WATER PIPING ALL MATERIALS USED SHALL NOT EXCEED 25 FOR FLAME SPREAD, 50 FOR FUEL SUPPLY THE CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, FEES REPRODUCED (IN WHOLE OR IN PART),SHARED <br /> DOMESTIC WATER PIPING 272" AND SMALLER SHALL BE COPPER TUBE WITH CONTRIBUTED, OR 50 FOR SMOKE DEVELOPED. UNLESS OTHERWISE REQUIRED BY IF WATER PRESSURE SUPPLIED TO STORE IS GREATER THAN AND 65 PSI. AND INSPECTIONS NECESSARY TO COMPLETE THE PLUMBING WORK. WITH THIRD PARTIES OR USED IN ANY MANNER <br /> WROUGHT COPPER SWEAT FITTINGS JOINED WITH NON-LEAD, NON-ANTIMONY SOLDER. THE LOCAL AUTHORITY OR ENERGY CODES, THE MINIMUM INSULATION LEVELS THEN PROVIDE A PRESSURE REGULATOR TO MAIN SUPPLY TO MAINTAIN WATER <br /> G G GAS PIPING PROVIDE TYPE BELOW GRADE. SHALL BE AS FOLLOWS: oNOTHERPROJECTS T EXTENSIONSTErHls <br /> L" COPPER TUBE ABOVE GRADE AND TYPE K <br /> TABLE 110.31 PRESSURE. PROVIDE BACKFLOW PREVENTION ON WATER SERVICE F REQUIRED BY WARRANTY PROJECT WITHOUT THE PRIOR WRITTEN <br /> PIPEINEULAIION TNICKNEW LOCAL CODES. THE CONTRACTOR SHALL UNCONDITIONALLY WARRANT ALL WORK TO BE CONSENT OF STARBUCKS CORPORATION. <br /> RD RD REFRIGERANT DISCHARGE PIPING CONDENSATE DRAINAGE PIPING NOxIXLLa xpxETEppn l".X«) FREE OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (111 THESE DRAWINGS AND SPECIFICATIONS ARE <br /> THE PLUMBING CONTRACTOR SHALL PROVIDE CONDENSATE DRAINS FOR AIR Ewm wxotnarpar PMRE MAN manaX .I Tm.ya rs N.a aa.e erne mwr YEAR FROM THE DATE OF FINAL ACCEPTANCE BY STARBUCKS AND WILL REPAIN INTENDED TO EXPRESS DESIGN INTENTFORA <br /> TENPEIU9IRE pv etwvmwrmvrwr xEwx Rprwc PROTOTYPICAL STARBUCKS STORE(WHICH IS <br /> RS REFRIGERANT SUCTION PIPING HANDLING UNITS AND STARBUCKS EQUIPMENT (REFER TO SCHEDULE). CONDENSATE RAXxE,cf) Wbn Ndwr+r TENPEppTURE I°P) INSU4TpXTKKXHE36 RE0UIREx IlnlueXpl <br /> RS DRAINAGE PIPING SHALL BE TYPE "M" COPPER TUBING WITH WROUGHT COPPER OR REPLACE ANY DEFECTIVE WORK PROMPTLY AND WITHOUT CHARGE AND <br /> Space nex;ng,no,wemr sysama Iaeeam,steam conaensax and to water)ave xrvice.ater ne.dng synems(recircmmmg arcennx SUBJECT TO CHANGE AT ANYTIME)AND DO <br /> SWEAT FITTINGS JOINED WITH 50/50 SOLDER. all piping In electric man land systems,and the End a ketofpiping from the merge lank forXeRR.:�rvmaeXg systema) I MISC. PLUMBING FIXTURE RESTORE ANY OTHER EXISTING WORK DAMAGED IN THE COURSE OF REPAIRING NOTREFLECT ACTUAL SITE CONDITIONS. <br /> �O� BV BALL VALVE neo"easo a.az-R.a4 o a.s so 0 o DEFECTIVE MATERIALS AND WORKMANSHIP. <br /> GAS PIPING NEITHER PARTY SHALL HAVE ANY OBLIGATION <br /> { GV GATE VALVE zmaso o.zv-a.az zso z.o a.a as as 4.5 I NOR LIABILITY TO THE OTHER EXCEPT STATED <br /> SHALL BE SCHEDULE 40 BLACK STEEL WOG BLACK BANDED MALLEABLE <br /> zoi-xso azno.m Iso zs zs zs ao so BACK FLOW PREVENTER ABOVE UNTIL WRITTEN AGREEMENT IS <br /> RON THREADED FITTINGS. BATTS ( ) ) <br /> Tal-zoo 0.25 0.29 Iu IS Is z.o zo za WATTS N0. SD-3 SIZE 3/8", ASSE 1022 APPROVED DUAL CHECK FULLY EXECUTED BY BOTH PARTIES. <br /> N CH. V CHECK VALVE GAS PIPING MATERIAL SHALL COMPLY WITH SEC. 1209.5 CPC l05-140 1 01211.2R 100 1.0 Ls Ls I is Ts WITH ATMOSPHERIC PORT DESIGN FOR PROTECTION OF THE WATER <br /> gpard cooling systems(cndiei wate,refagenvt and tine) SUPPLY FROM CARBON DIOXIDE GAS, CARBONATED WATER & DISPENSING <br /> o RV RELIEF VALVE Nonni Res None, Re, ARCHITECT OF RECORD <br /> = HANGERS & SUPPORTS oow 0..zi-0.27 7s os Re' os a.7s 1.o Lo Lo EQUIPMENT. 316 STAINLESS STEEL BODY CONSTRUCTION. n1Cg BFCNIteCtOFB <br /> THE PLUMBING CONTRACTOR SHALL FURNISH ALL PIPE SUPPORTS REQUIRED FOR <br /> m Io <br /> HB HOSE BIBB EQUIPMENT AND MATERIAL. ALL HORIZONTAL RUNS OF PIPING SHALL BE eNew ao o.zoo.zc so Ls <br /> U Ls Ls Ls ` <br /> , <br /> SUPPORTED BY PIPE HANGERS INSTALLED AS REQUIRED BY LOCAL CODES d � <br /> ❑s ADDITIONAL SUPPORTS SHALL BE PROVIDED WHERE REQUIRED TO PREVENT PIPE MARKERS: <br /> x8 SHOCK ABSORBER SAGGING. HANGERS AND PIPE ATTACHMENTS TO BE FACTORY FABRICATED WITH <br /> w GALVANIZED COATINGS; NONMETALLIC COATED FOR HANGERS IN DIRECT CONTACT PROVIDE INSULATED PIPES WITH PIPE MARKERS, 8° LONG AND DESIGNED y <br /> STRAINERWITH COPPER TUBING. FOR SNAP AROUND PARELLEL MARKING. COLD WATER SHALL BE INDENIIFIED WITH <br /> BUCK LETTERING AGAINST A GREEN BACKGROUND; HOT WATER SHALL BE INDENNFlED 111 Pacifica,Suite 280,Irvine,CA 92618 <br /> r1 CO WALL CLEANOUT CONNECTIONS BY BLACK LETTERING AGAINST A YELLOW BACKGROUND, P:949.553.1117 F:949.474.7056 <br /> 0DINSTALL UNIONS ADJACENT TO EACH VALVE AND AT FINAL CONNECTION TO EACH SAFETY COVERS: <br /> In JzFCO FLOOR CLEANOUT PIECE OF EQUIPMENT. INSTALL DIELECTRIC COUPLINGS TO CONNECT PIPING INSTALL SPECIFIED NO-SCALD SAFETY COVERS WITH INSULATED FOAM LINER AND ARCHITECT STAMP RpFESSIONq <br /> m MATERIALS OF DISSIMILAR METALS. SCREW JOINT STEEL PIPING UP TO AND TAMPER PROOF STRAP AS FURNISHED BY STARBUCKS AT ALL EXPOSED PIPING. <br /> UI FS FLOOR SINK INCLUDING 1-1/2". WELD PIPING USE NON-LEAD, NON-ANTIMONY SOLDER FOR <br /> SOLDERING DOMESTIC WATER COPPER PIPE. ICE BIN DRAIN: v Z <br /> v INSULATE ICE BIN COPPER DRAIN UNES WITH 4' THICK, SELF-SFAUNG, SECTIONAL, � o. 24509 m <br /> WM WATER METER CLEANOUTSCLOSED CELL FOAM. Ex .9-30-2018 A <br /> y PROVIDE J.R. SMITH OR EQUIVALENT FLOOR AND WALL CLEANOUTS AS INDICATED HVAC PIPING: <br /> m CONNECT TO EXISTING ON THE DRAWINGS OR WHERE REQUIRED BY CODE IN ALL SOIL, WASTE, AND DRAIN INSULATE REFRIGERANT SUCTION PIPING AND COOLING COIL CONDENSATE PIPING b£ <br /> ILL. LINES. IN AREAS WITH CERAMIC TILE OR CARPETED FLOORING, PROVIDE CLEANOUTS WITH ''a THICK, SELF SEALING, CLOSED CELL FOAM. INSULATE HVAC HOT AND qT CHANE R�\P <br /> WITH SQUARE, ADJUSTABLE, NICKEL BRONZE TOP. IN AREAS WITH RESILIENT CHILLED WATER PIPING SYSTEMS AND LOW PRESSURE STEAM AND CONDENSATE FOF CAV.\FO <br /> FLOORING, PROVIDE CLEANOUTS WITH SQUARE, ADJUSTABLE, NICKEL BRONZE TOP PIPING WITH 1-1/2" THICK, HEAVY DUTY, SELF SEALING, JACKETED FIBERGLASS. <br /> tY WITH TILE RECESS. CLEANOUTS SHALL BE SAME SIZE AS PIPE EXCEPT THAT <br /> CLEANOUTS LARGER THAN 4" WILL NOT BE REQUIRED. WHERE CLEANOUTS OCCUR IN RAIN CONDUCTORS: <br /> O WALLS OF FINISHED AREAS, THEY SHALL BE CONCEALED BEHIND CHROME PLATED INSULATE RAIN WATER CONDUCTORS WHICH PASS THROUGH OCCUPIED AREAS <br /> U ACCESS COVERS. WITH Y2" THICK FIBERGLASS. <br /> ENVIRONMENTAL HEALTH NOTES: BLDG. DEPARTMENT NOTES : <br /> N <br /> 1. A CONCRETE SLAB IS PROVIDED FOR TRASH, GARBAGE, AND GREASE CONTAINER. 13. ALL WAREWASHING SINKS TO HAVE 3 CONPARTMENTS THAT ARE A MINIMUM SIZE 26. APPROVED BACKFLOW PREVENTION DEVICES SHALL BE PROPERLY INSTALLED 36. BACKUP DRY STORAGE SHELVING SHALL BE A MINIMUM OF 96 LINEAR FEET LAVATORY FAUCETS IN RESFROOMS SHALL BEE THE METERED OR SELF-CLOSING TYPE. <br /> IF WALLS ENCLOSE AREA, THE INTERIOR WALL SURFACES WILL BE SMOOTH, SEALED OF AT LEAST 18"x18"x12" DEEP (OR 16"x20"x12" DEEP) WITH A MINIMUM 18" UPSTREAM OF ANY POTENTIAL HAZARD BETWEEN THE POTABLE WATER SUPPLY (MEASUREED WITH TIERS) OR 25% OF KITCHEN, FOOD PREP, AND WORK O <br /> AND WASHABLE (E.G. PLASTERED SMOOTH AND PAINTED, ETC.) DRAINBOARD AT EACH END. IF AGAINST A WALL, IT MUST HAVE AN B" INTEGRAL AND A SOURCE OF CONTAMINATION. HOSES SHALL NOT BE ATTACHED TO A AREAS, WHICHEVER IS GREATER. SHELVING SHALL BE AT LEAST 18 INCHES EACH FAUCETS SHALL NOT EXCEED A WATER ROW OF 1.8 GPM. <br /> BACKSPLASH. HOWEVER, IT MUST BE CAPABLE OF ACCOMMODATING THE LARGEST FAUCET OR HOSE BIBB UNLESS AN APPROVED BACK FLOW PREVENTER IS DEEP AND START A MINIMUM SIX INCHES OFF THE FLOOR SURFACE. TOILETS SHAM BE ULTRA LOW FLUSH TYPE(1.28 G.P.F. MAX.) O <br /> U PROVIDED. z: <br /> 2. ALL FOOD-RELATED AND UTENSIL-RELATED EQUIPMENT SHALL MEET OR BE UTENSIL TO BE WASHED. A WAREWASHING MACHINE DOES NOT SUBSTITUTE FOR <br /> m EQUIVALENT TO SANITATION STANDARDS ESTABUSHED BY AN AMERICAN NATIONAL THE SINK REQUIREMENT. 39. SHELVING OVER WET AREAS (SINKS, MOP SINKS ETC.) AND FOOD PREP CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER SUPPUED APPLIANCES <br /> F STANDARDS INSTITUTE (ANSI) ACCREDITED PROGRAM. 27. WATER SUPPLY TO CARBONATORS SHALL BE PROTECTED BY AN APPROVED SURFACES WILL BE METAL. AND EQUIPMENT (OTHER THAN THOSE LISTED IN INFORMATION BULLETIN 103). L co <br /> 1 14. SINKS TO HAVE SPOUT(S) CAPABLE OF REACHING EACH COMPARTMENT. REDUCED PRESSURE PRINCLPLE BACKFLOW PREVENTER. THE RELIEF VALVE SHALL L �' <br /> 3 DRAIN INDIRECTLY TO SEWER WITH A LEGAL AIR GAP. 40. ALL SEAMS, GAPS, OPENINGS TO BE PROPERLY SEALED. INSTALLATION OF SOIL OR DRAIN PIPES IN FOOD HANDUNG ESTABLISHMENT WILL COMPLY WITH L U M <br /> 0 3. ALL FLOOR MOUNTED EQUIPMENT WILL BE INSTALLED ON MINIMUM 6" SANITARY to <br /> o LEGS, CASTORS, OR COMPLETELY SEALED IN POSITION ON A 4" HIGH CURB WITH 15. FOOD PREP SINK COMPARTMENT(S) TO BE AT LEAST 18"x18"x12" DEEP (OR SECTION 318.0 CPC 2016 LU <br /> LU LOFOR CLEANING FLOOR MATS, THE JANITORIAL SINK TO BE A MINIMUM 24" BY 36" <br /> CONTINUOUSLY COVED BASE. COUNTERTOP EQUIPMENT WILL BE ON 4-INCH 16"x20"x12" DEEP) WITH A MINIMUM 18" DRAINBOARD. SEPARATE FOOD PREP WATER CLOSET BOWLS SHALL BE ELONGATED TYPE AND SEATS AND SEATS SHALL BE OPEN FRONT � O �- <br /> SANITARY LEGS OR SEALED TO THE COUNTER UNLESS READILY MOVABLE. SINKS TO BE PROVIDED FOR MEATS AND PRODUCE. FLOOR-MOUNTED TYPE. MOPS SHALL BE PLACED IN A POSTION THAT ALLOWS TYPE. SEC. 408.1, 408.2 CPC 2016 z Q Q <br /> o THEM TO AIR-DRY WITHOUT SOILING WALLS, EQUIPMENT, OR SUPPLIES. p6 j U <br /> 4. IF SOFT DRINK, ICE OR OTHER DISPENSERS ARE SELF-SERVICE, OR IF REFILLS 16. THE 3 OR 4 COMPARTMENT BAR SINK TO BE AT LEAST 12"x12"x10" DEEP (OR ALL FIXTURES EQUIPMENT, PIPING AND MATERIALS SHALL BE LISTED PERMANENT VACUUM BREAKERS SHALL BE INCLUDED WITH ALL HOSE BIBS. U U > - <br /> Y ARE PROVIDED THEY MUST BE PUSH BUTTON TYPES, OR LEVER TYPES WHERE THE 29. THE JANITORIAL SINK FAUCET WILL HAVE A THREADED OUTER LIP FOR HOSE w LU <br /> _ LEVER CONTACTS THE CONTAINER AT LEAST ONE INCH BELOW THE RIM. 10"x14"x10" DEEP) WITH A MIMUM 18" DRAINBOARD AT EACH END. �... <br /> ATTACHMENT AND A APPROVED BACK FLOW PREVENTION DEVICE. NO CHECMICAL ALL PLUMBING FIXTURES SHALL MEET THE FLOW REQUIREMENTS SPECIFIED WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT O O ca <br /> DISPENSING SYSTEMS OR SHUTOFF VALVES TO BE ATTACHED TO MOP SINK o De OD <br /> X01 5. ANY OPENABLE WINDOWS VENT OIPENINGS OR OTHER SIMILAR OPENINGS MUST BE 17. A SEPARATE WET WASTE DUMP FIXTURE SHALL BE PROVIDED FOR DISPOSAL OF FAUCET OUTLET (UNLESS A "SIDEKICK" PLUMBING DEVICE IS INSTALLED). IN THE CALFORNIA PLUMBING CODE DUE TO EARTHRQUAXE MOTION PER SECTION 508.2 CPC. SEE DETAL5 SHEET P4 a a �. <br /> DRINK OR WASTE ICE OR COFFEE WASTE. <br /> � PROVIDED WITH TIGHT FIRING SCREENS OF MINIMUM 16-MESH TO THE INCH. ALL FAUCETS IN PUBUC RESTROOMS SHALL BE SELF-CLOSING OR SELF FLOOR DRAINS OR SIMILAR TRAPS DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM AND SUBJECT <br /> WINDOWS TO BE FIXED AT FOOD PREP, UTENSIL-WASHING, OPEN FOOD AND 30. NO CONDENSATE OR WASTEWATER INCLUDING HVAC WILL DRAIN INTO THE TO INFREQUENT USE SHALL BE PROVIDED WITH AN APPROVED AUTOMATIC MEANS OF MAINTAINING STORE #: 5875 <br /> X 17.1.EACH HANDWASHING SINK MUST HAVE PERMANENTLY MOUNTED CLOSING METERING FAUCETS <br /> I UTENSIL STORAGE AREAS. SINGLE-SERVICE SOAP AND PAPER TOWEL DISPENSERS. JANITORIAL SINK. THEIR WATER SEALS. PROJECT #: 08798-038 <br /> U1 PUBLIC LAVATORIES SHALL HAVE CONTROLS TO LIMIT THE WATER <br /> N 6. ALL EXTERIOR DOORS OPEN OUTWARD AND ARE SELF-CLOSING AND TIGHT FIITING. 19, THE HOT WATER HEATER WILL BE A COMMERCIAL TYPE CAPABLE OF CONSTANTLY 31. GREASE TRAP TO BE LOCATED OUTSIDE THE FOOD SERVICE ACTIVITY AREA, FLUSH TEMPERATURE TO 110"F (TITLE 24 PART 6 110.3(C)3) ALL PLUMBING, ELECTRICAL AND GAS UNES SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE PROFILE TYPE: CORE <br /> WITH THE FINISHED FLOOR WHEN INDOORS. LOCAL WASTEWATER DISTRICT OR ISSUE DATE: <br /> It SUPPLYING HOT WATER AT A TEMPERATURE OF 129F TO ALL SINKS. IN SIZING BUILDING DEPARTMENT TO BE CONTACTED FOR GREASE REMOVAL REQUIREMENTS. TO AS GREAT AN EXTENT AS POSSIBLE. ALL EXPOSED CONDUITS, PLUMBING, ETC. SHALL BE INSTALLED PROGRAM MANAGER: M. MONTENEGRO <br /> 7. BI-FOLD, FRENCH, ACCORDION STYLE AND ROLL-UP DOORS CANNOT OPEN INTO THE WATER HEATER, THE PEAK HOURLY DEMAND FOR ALL SINKS, ETC., ARE WATER PIPE AND FITTINGS WITH A LEAD CONTENT WHICH EXCEEDS 0.25% AT LEAST 6"OFF FLOOR AMD 3/4"FROM THE WALLS USING STANDOFF BRACKETS. <br /> C6 THE FOOD PRP, UTENSIL WASHING OR UNPACKAGED FOOD SERVICE AREAS. SHALL BE PROHIBITED IN SYSTEMS CONVEYING POTABLE WATER. STORE DESIGNER: <br /> y ADDED TOGERTHER TO DETERMINE THE MINIMUM REQUIRED RECOVERY RATE. <br /> v 32. FLOOR DRAINS SHALL BE INSTALLED IN FLOORS THAT ARE WATER-FLUSHED FOR BUILDING DRAIN AND VENT PIPING MATERIALS SHALL COMPLY WITH SECTIONS 701.0 AND 903.0 OF THE LEED'U AP: <br /> .0 8. TOILET ROOM AND DRESSING ROOM DOORS MUST BE SELF-CLOSING, TIGHT FITTING. 20. ALL LAVATORIES OR HAND SINKS WILL HAVE A COMBINATION FAUCET OR CLEANING AND IN AREAS WHERE PRESSURE SPRAY METHODS FOR CLEANING CALIFORNIA PLUMBING CODE CHECKED BY: <br /> m EQUIPMENT ARE USED, IN RESTROOMS, JANITORIAL ROOMS, SCULLERIES, AND AT <br /> 9. DELIVERY DOORS TO HAVE AIR CURTAIN FANS THAT SPAN THE WIDTH OVER THE PREMIXING FAUCET CAPABLE OF SUPPLING WATER TEMPERED TO 100°F. MCG PROJECT#: 16420 <br /> to BARS WITH 1:50 TO <br /> THE FLOOR SURFACES IN AREAS PURSUANT TO THIS SHALL ALL SANITARY SYSTEM MATERIALS SHALL BE LISTED BY AN APPROVED USNNG AGENCY. <br /> DOOR. THE FAN MUST ACTIVATE VIA A MICROSWITCH PROVIDING A MINIMUM SELF-CLOSING OR METERED FAUCET TO PROCIDE AT LEAST 15 SECONDS OF BE SLOPED 1:50 TO THE FLOOR DRAINS. MCG PROD. MANAGER: c.LEE <br /> w VELOCITY OF 1600 FPM MEASURED 3 FEET ABOVE GROUND. WATER WITHOUT REACTIVATION. POTABLE WATER PIPING MATERIAL SHALL COMPLY WITH SEC. 604.0 CPC 2016 MCG PROJ. SPECIALIST: L.COSTA <br /> cUi33. ADEQUATE VENTILATION IS TO BE PROVIDED TO ALL TOILET ROOMS, JANITOR <br /> .0 21. ALL PLUMBING, ELECTRICAL AND GAS LINES SHALL BE CONCEALED WITHIN THE CLOSETS WITH MOP SINKS, AND INDOOR TRASH ROOMS AND IN EACH FAUCET SHALL NOT EXCEED A WATER FLOW OF 2.2 GPM. Revision Schedule <br /> a 10. A MINIMUM OF 10 FOOT-CANDLES OF LIGHT MEASURED 30" OFF FLOOR IS BUILDING STRUCTURE TO AS GREAT AN EXTENT AS POSSIBLE. ALL EXPOSED <br /> PROVIDED IN WALK-IN REFRIGERATED STORAGE AND DRY STORAGE ROOMS AND AT DRESSING/CHANGE ROOM(S). <br /> m CONDUITS, PLUMBING, ETC. SHALL BE INSTALLED AT LEAST 6° OFF BOOR AND CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER SUPPLIED APPLIANCES Rev Date By Description <br /> 10 <br /> LEAST 20-FOOT CANDLES IS PROVIDED WHERE FOOD IS PROVIDED FOR CONSUMER ^ FROM WALLS USING STANDOFF BRACKETS. 34. THE FLOOR FINISH WILL HAVE A SMOOTH SURFACE UNDER ALL EQUIPMENT AND AND EQUIPMENT (OTHER THAN THOSE LISTED IN INFORMATION BULLEITN 103). <br /> cy SELF-SERVICE, WHERE FRESH PRODUCE OR PREPACKAGED FOODS ARE SOLD OR <br /> OFFERED FOR CONSUMPTION; INSIDE EQUIPMENT SUCH AS REACH-IN ANDp2CONDUITS, PLUMBING OR PIPING CANNOT BE INSTALLED ACROSS ANY AISLE WAY, WALKWAYS WILL HAVE A LIGHT TEXTURE ONLY. <br /> , <br /> UNDER-COUNTER REFRIGERATORS; IN AREAS USED FOR HANDWAHSING, TRAFFIC AREA OR DOOR OPENING. <br /> WAREWASHING, EQUIPMENT AND UTENSIL STORAGE, AND IN TOILET ROOMS. THE PAINT USED ON WALLS AND CEILINGS OF ALL KITCHEN, FOOD PREPATATION, <br /> 23. MULTIPLE RUNS OR CLUSTERS OF CONDUIT OR PIPELINES SHALL BE FURRED IN WORK, AND STORAGE AREAS WILL BE A GLOSS OR SEMI-GLOSS ENAMEL. FlNSH <br /> MATERIAL SHALL BE A UGHT COLOR IN FOOD PREP AREAS FOR EASY CLEANING. ® TITLE: <br /> Q 11. A MINIMUM OF 50 FOOT-CANDLES OF LIGHT MEASURED 30" OFF FLOOR IS OR ENCASED IN AN APPROVED SEALED ENCLOSURE. SHEET PROVIDED WHEN WORKING WITH FOOD OR WORKING WITH UTENSILS OR EQUIPMENT 35. PRIOR TO INSTALLATION, SAMPLES OF FINISHES TO BE SUBMITTED TO PLUMBING NOTES <br /> Et SCHEDULES <br /> SUCH AS KNIVES, SUCERS, GRINDERS, OR SAWS WHERE EMPLOYEE SAFETY IS A 24. ALL LIQUID WASTE SHALL BE DRAINED BY MEANS OF INDIRECT WASTE PIPES INTO <br /> in FACTOR AND IN ALL AREAS DURING PERIODS OF CLEANING. ENVIRONMENTAL HEALTH FOR APPROVAL AS NEEDED. <br /> A FLOOR SINK. FLOOR SINKS ARE TO BE INSTALLED FLUSH WITH THE FINISHED rP2 <br /> ING SHEET INDEX: <br /> 12. SHATTERSHIELDS FOR ALL LIGHTS ABOVE FOOD PREPARATION, WORK AND STORAGE FLOOR SUREFACE AND HAVE SUITABLE EASILY REMOVABLE SAFETY COVER GRATES. 36. COLD STORAGE ROOMS SHALL BE PROVIDED WITH A SECTION OF SHELVING Erzprzeers, 4tc. SCALE:AS SHOWN <br /> N AREAS WILL BE PROVIDED. INSTALLED TO HOLD SHALLOW COOL DOWN PANS -NOT TO EXCEED 4° IN HEIGHT. ..Plumbing Notes & Schedules. 102 DISCOVERY <br /> 25. FLOOR SINK TO BE 50% EXPOSED WHEN NO ACCESS IS PROVIDED FOR CLEANING Irvine, 9Ca.-4 0-1; SHEET NUMBER: <br /> m <br /> OR BE IN UNE WITH THE FRONT FACE OF ELEVATED FREESTANDING EQUIPMENT. SPACE BETWEEN SHELVING TO BE AT LEAST 8" HIGH. ..Hot�Cold Water Plumbing Plan Telr 949-450-12K0..Waste & Vent Plumbing Plan Contact: <br /> Jose B l a 5a219 <br /> RPM #17-002Z <br />