Laserfiche WebLink
Site Address: 1231 N. Main Street, Manteca <br />04/30/2019 <br />Record ID# SR0077446 <br />Program: UST <br />Photo 4: Ending image of the diesel tank gauge at 4.1 psi for post tank installation pressure testing at 5 psi per 1 hour. The tank pressure <br />decreased from 5.1 psi to 4.1 psi. <br />Shewit Woldearegay, EHS Page 4 of 4 <br />