SANJ O 1` Q U I `IA,II, Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AMERON INTERNATIONAL 1 10100 W LINNE RD,TRACY January 08, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 706 CFR 112.8(c)(2)Failed to provide and maintain adequate secondary containment. <br /> The emergency gnerator was observed with insufficient secondary containment. There was no evident secondary <br /> containment for the belly tank of the generator. All bulk storage tanks must be provided with a secondary means of <br /> containment for the entire capacity of the tank and sufficient freeboard to contain precipitation. Immediately provide <br /> sufficient secondary containment for this and all other tanks at this facility. <br /> This is a Class II violation. <br /> 711 CFR 112.8(c)(6)Failed to perform scheduled tank tests or inspections by appropriately qualified personnel. <br /> The 10,000 gallon tank was not tested on schedule by qualified personnel. The SPCC plan calls for formal STI <br /> SP-001 inspections by a certified SP-001 inspector every 10 years.The tank is older than ten years and a formal <br /> inspection has not been conducted.Also,the inspection/testing of the onsite mobile refueler must be addressed in <br /> the SPCC plan. Each aboveground container shall be tested and inspected for integrity on a regular schedule and <br /> whenever repairs are made. The qualifications of personnel performing tests and inspections,frequency and type <br /> of testing and inspections that take into account container size, configuration, and design shall be determined in <br /> accordance with industry standards. Examples of these integrity tests include, but are not limited to: visual <br /> inspection, hydrostatic testing, radiographic testing, ultrasonic testing, acoustic emissions testing, or other systems <br /> of non-destructive testing. Comparison records and other records of inspections and tests must be maintained on <br /> site. Immediately conduct the necessary testing and submit a copy of the test results to the EHD and address <br /> testing/inspections for all qualified tanks per industry standards or provide equivalence as allowed by CFR 112.7(a) <br /> (2)• <br /> This is a Class II violation. <br /> 717 CFR 112.8(c)(10) Failed to promptly correct visible discharges and/or remove accumulations of oil in diked areas. <br /> A sheen was observed on the water in the retention pond. Sheen was observed between the boom and the pipe <br /> which water flows into the pond. Promptly correct visible discharges which result in a loss of oil from the container, <br /> including but not limited to seams, gaskets, piping, pumps, valves, rivets, and bolts.You must promptly remove any <br /> accumulations of oil in diked areas.. Immediately remove oily substance from pond, and manage according to the <br /> California Code of Regulations Title 22 hazardous waste regulations. <br /> This is a Class II violation. <br /> FA0004382 PR0515795 SCO01 01/08/2019 <br /> EHD 28-01 Rev.09/27/2018 Page 5 of 6 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />