Laserfiche WebLink
Item 102: <br /> 112.8(a) Discharge prevention and containment are discussed pages 11, 13,15,20 <br /> 112.8(b) Facility Drainage discussed page 13 <br /> 112.8Lc JBulk Storage Containers 13 <br /> Item 301: <br /> The referenced oil tank over 100 gallons is not in service. McLane will remove it and the other 2 100 gallon tanks since <br /> they are not in use.The referenced generator allegedly having a tank larger than 55 gallons is not in use and has been <br /> labeled as such. 15,000 gallon ASTs changed to "single wall". <br /> Item 601: <br /> Added reference to 112.7(g) below security description on page 10. Added references to 112.8(a) and 112.8(b). <br /> Item 603: <br /> Added reference to diagram to "See following Page 20 for details". Added piping to the diagram. <br /> Item 604: <br /> The plan specifically lists each container, etc. on page 20. <br /> Item 609: <br /> Reporting procedures discussed on Page 14. Added CUPA's phone number on page 14. <br /> Item 612: <br /> Tanks in "maintenance building" do not belong to McLane and were removed from the plan.The "sewer" drain is sealed. <br /> The three smaller tanks at the fuel island are not in use and will be removed from the fuel island.They have been <br /> removed from the plan. 15,000 gallon ASTs changed to "single wall". <br /> Item 618: <br /> Monthly inspections started 01/31/19. <br /> Item 628: <br /> 112.7(a)(1) specifically discussed on page 10 and included in original cross reference. Added statement "There are no <br /> known more stringent State rules, regulations and guidelines that exceed the requirements of this SPCC Plan" on page <br /> 10. <br /> Item 711: <br /> Integrity tests for Tanks 1 and 2 are planned to be completed during fuel island overhaul. Date TBD. <br /> Item 720: <br /> Piping installed prior to August 16, 2002. <br /> Item 723: <br /> Monthly Inspection form specifically lists "Piping Connections"to be inspected for leaks, Corrosion, or Damage on page <br /> 24.Annual Inspection Procedure includes the following statement at the beginning: "Visually inspect containers for any <br /> indication of the need for repair, maintenance, or replacement including man way gaskets and piping connections" on <br /> page 22. <br />