Laserfiche WebLink
SANJO A Q U I N Environmental Health Department <br /> C C-) U N `l Y it <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name : Facility Address : Date : <br /> Lawrence Livermore National Lab - Site 300 J15999 W CORRAL HOLLOW RD , TRACY November 26 , 2018 <br /> Other Violations <br /> 4040 See below Unlisted Release/Leaks/Spills violation ❑ V ❑ R ❑ COS <br /> 4050 See below Unlisted Abandon ment/IIlegal Disposal/Unauthorized Treatment violation ❑ V ❑ R ❑ COS <br /> SUMMARY OF VIOLATIONS <br /> ( CLASS I , CLASS II , or MINOR - Notice to Comply ) <br /> Item # Remarks <br /> 105 CFR 11201 ( b ) ( 3 ) , 112 . 2 Failure to properly close tanks when making a claim of permanently closed . <br /> A portable generator with a diesel tank of a capacity of over 55 gallons was said to be permanently closed . The <br /> generator was located in the parking area of the 875 building . The generator' s diesel tank is not in use but has not <br /> been properly closed . The tank was missing a sign conspicuously stating that it is a permanently closed container <br /> and denoting the date of closure . When a tank is not in use , it must be permanently closed by meeting the following <br /> conditions : <br /> - remove all liquid and sludge from each container and connecting line <br /> - disconnect and blank off all connecting lines and piping have from the tank <br /> - close and lock all valves <br /> - post a sign conspicuously stating that it is a permanently closed container and denoting the date of closure . <br /> Immediately " Permanently Close" all tanks that are not being used or amend the Spill Prevention , Control , and <br /> Countermeasure Plan to include all petroleum tanks that have not been permanently closed . <br /> This is a minor violation. <br /> 618 CFR 112 . 7 ( e ) , 112 . 8 ( c) (6 ) Failed to keep records of procedures , inspections , or integrity tests for three years . <br /> Copies of annual inspection records were not found on site for tanks 879TF001 , 879TF002 , 875TF003 and <br /> 875TF002 . SPCC plan calls for monthly and annual inspections per STI SP001 standards . Inspections and tests <br /> must be conducted in accordance with the written procedures developed in the Spill Prevention , Control , and <br /> Countermeasure ( SPCC) Plan. Records of these inspections and tests must be signed by the appropriate <br /> supervisor or inspector and kept on site with the SPCC Plan for a period of three years . Immediately locate a copy <br /> of all inspection and testing records for the last three years , maintain them on site , and submit copies to the EHD . <br /> This is a Class II violation. <br /> Overall Inspection Comments . <br /> This is an amended copy of the original inspection report dated 11 /26/2018 . This amended version supersedes <br /> any previous versions of the report . This report was amended on 01 / 15/2019 . A return to compliance has been <br /> received addressing the original violations on the report , all violations have been addressed . <br /> Starting September 1 , 2018 , all in -office CERS help will be provided at EHD hourly rate ($ 152 ) . To schedule an <br /> appointment , please call (209 ) 468 -3420 . <br /> AFTER THE COMPLIANCE DATE , EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE . <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD ' S CURRENT HOURLY RATE . <br /> Received by : Date : November 26 , 2018 Inspector : Inspector Phone : <br /> Printed Name and Title: CESAR RUVALCABA , REHS (209 ) 953 -6213 <br /> Valerie Dibley, Acting Site 300 Manager <br /> FA0003934 PR0528989 SCO01 11 /26/2018 <br /> EHD 28-01 Rev. 09/27/2018 Page 4 of 4 Aboveground Petroleum Storage Act OIR <br /> 1868 E . Hazelton Avenue Stockton , California 95205 1 T 209 468 - 3420 F 209 464 -0138 I www . sjcehd . com <br />