My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2019
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
Y
>
YOSEMITE
>
2072
>
2300 - Underground Storage Tank Program
>
PR0231426
>
COMPLIANCE INFO_2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/17/2023 3:27:12 PM
Creation date
1/18/2019 11:57:07 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2019
RECORD_ID
PR0231426
PE
2361
FACILITY_ID
FA0004625
FACILITY_NAME
NATIONAL PETROLEUM MANTECA
STREET_NUMBER
2072
Direction
W
STREET_NAME
YOSEMITE
STREET_TYPE
AVE
City
MANTECA
Zip
95337
APN
22202001
CURRENT_STATUS
01
SITE_LOCATION
2072 W YOSEMITE AVE
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
132
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
AMENDEDEnvironmental Health Department <br /> SAN JOAQUIN 1116117 <br /> C. i_) U I�� I Y - - - <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name : Facility Address : Date : <br /> QUICK SHOP 2072 W YOSEMITE AVE , MANTECA December 18 , 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I , CLASS II , or MINOR - Notice to Comply) <br /> Item # Remarks <br /> 111 CCR 2638 ( a ) & ( b) , 26410 ) Failed to test monitoring and leak detection equipment annually . <br /> 1 ) Annual monitoring system certification and leak detector testing were last performed on 9/ 19/ 17 and was <br /> completed on 12 / 18/ 18 , 3 months past due . These tests are required once every 12 months . Take all necessary <br /> precautions to ensure testing is performed in a timely manner . <br /> The operator provided a statement to close this part of the violation while the inspector was on site . <br /> 2 ) When the inspector arrived on site , the service technician had indicated that he conducted the leak detector test <br /> for the 100 octane and 110 octane product tank . When the inspector asked how the test was conducted since the <br /> amount of fuel in both tanks was low, the service technician ( Felix Ramirez ) stated the the automatic tank gauge <br /> was removed from the tank to move the float to a higher level in order to " override" the system to allow the turbine <br /> run . The service technician ran the leak detector test for the 100 octane and 110 octane product tanks with the <br /> automatic tank gauge outside the tanks and not in operating conditions . Based on code section 2638 ( a ) "All <br /> monitoring equipment used to satisfy the requirements of this article shall be installed , <br /> calibrated , operated and maintained in accordance with manufacturer' s instructions , and certified every 12 months <br /> for operability, proper operating condition , and proper calibration " . Ensure to perform leak detection test on 100 <br /> octane and 110 octane schedule this test , providing a 48 hour notice to EHD while the 100 octane and 110 octane <br /> tanks are in operating condition upon fuel delivery within 30 days from receiving this amended report . <br /> This is a repeat violation , Class II . <br /> 113 CCR 2638 (c) , 2638 (d ) Failure to submit " Monitoring System Certification Form" within 30 days of completion of the <br /> test . <br /> Annual monitoring system certification , leak detector testing , and spill container testing was performed on 9/ 19/ 17 <br /> and a test report was submitted on 3 /23/ 18 , 6 months late . A copy of the test report must be submitted within 30 <br /> days of the tests . Take all necessary precautions to ensure testing and submittal of test reports are performed in a <br /> timely manner . <br /> The operator provided a statement to close this violations while the inspector was on site . <br /> This was corrected on site . <br /> This is a repeat violation , Class ll . <br /> FA0004625 PR0231426 SC333 12/18/2018 <br /> EHD 23-01 Rev. 09/28/2018 Page 5 of 9 Underground Storage Tank Program OIR <br /> 1868 E . Hazelton Avenue Stockton , California 95205 1 T 209 468 - 3420 F 209 464 - 0138 1 www . sjcehd . com <br />
The URL can be used to link to this page
Your browser does not support the video tag.