Laserfiche WebLink
CUSTOMER: ARCO DATE: 4-6-89 I.D. NC 6100 <br />ADDRESS: 25775 S. PATTERSON ..ASS <br />TRACY, CA <br />FINAL TEST RESULTS SUMMARY <br />LEAK LOKATOR RESULTS <br />SYSTEM TANK SIZE WATER LEVEL ALR RECOMMEN- <br />NO PRODUCT GALLONS DIA/MATL INCHES INCHES GPH CONCLUSION DATIONS <br />1 SU U/L <br />6,000 <br />92 <br />0 <br />163 +.003 <br />PASS <br />2 U/L #1 <br />6,000 <br />92 <br />0 <br />154 +.021 <br />PASS <br />U/L #2 <br />6,000 <br />92 <br />0 <br />1H <br />2.521 <br />3 REG #1 <br />6,000 <br />92 <br />0 <br />142 +.019 <br />PASS <br />REG #2 <br />6,000 <br />92 <br />0 <br />1H <br />2.521 <br />+10.323 <br />PRODUCT <br />LINES <br />- HYDROSTATIC <br />PRESSURE TEST <br />RESULTS <br />SYSTEM TYPE OF PUMP POUNDS POUNDS MINUTES PRODUCT PRODUCT CONCLUSION <br />NO PRODUCT REMOTE SUCTION APPLIED HELD HELD LOSS CC's LOSS GPH /RESULT <br />1 SU U/L RJ 50 50 15 PASS <br />2 U/L RJ 50 50 15 PASS <br />3 REG RJ 50 50 15 PASS <br />LEAK DETECTOR TEST <br />NO. PRODUCT FULL OPEN POSITION CLOSED FOR RESULTS <br />FOR 30 SECONDS 30 SECONDS <br />1 REG 1 GAL. <br />2 U/L 1 GAL. <br />3 SU U/L 1 GAL. <br />DETAIL OF TEST RESULTS <br />3 GAL. PASS <br />3 GAL. PASS <br />3 GAL. PASS <br />TEST TIME TEMPERATURE ABSOLUTE CHECK <br />SYSTEM TEST LEVEL CLOCK DURATION LEAK RATE COMPENSATION LEAK RATE TEST <br />NO. PRODUCT NO. (IN.) START (HR -MIN) CC/DIV CC/MIN DELTA OF CC/MIN CC/MIN GPH Y/N <br />1 SU U/L <br />1 <br />163 <br />9:40 <br />1H <br />2.142 <br />+1.993 <br />+.007 <br />+1.747 <br />+.246 <br />+.003 N <br />2 U/L <br />#1 <br />1 <br />154 <br />11:20 <br />1H <br />2.521 <br />+10.323 <br />+.012 <br />+2.997 <br />+1.331 <br />+.021 N <br />U/L <br />#2 <br />1 <br />154 <br />11:20 <br />1H <br />2.521 <br />+10.323 <br />+.024 <br />+5.995 <br />+1.331 <br />+.021 N <br />3 REG <br />#1 <br />1 <br />142 <br />2:00 <br />1H <br />8.333 <br />+.992 <br />+.007 <br />+1.748 <br />+1.242 <br />+.019 N <br />REG <br />#2 <br />1 <br />142 <br />2:00 <br />lH <br />8.333 <br />+.992 <br />+.008 <br />+1.998 <br />+1.242 <br />+.019 N <br />*LEVEL - Inches from Tank Bottom to Test Level <br />AIR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in <br />Gallons Per Hour. <br />CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness. <br />This is to certify that the above tank systems were tested, using the HUNTER <br />ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. <br />Those indicated as tight at full system meet the criterion established by the National <br />Fire Protection Assn. Pamphlet 329 for Precision Testing. <br />Date Test Conducted: 4-6-89 Team Manager: STEVE ANDERSON Associate: EMMA ANDERSON <br />Test Certification By: Pat Wheeler, Operations Manager <br />Hunter Environmental <br />597 Center Avenue, Suite 350 CED11FIE" <br />Martinez, CA 94553 <br />(1-800) 321-3637 <br />A:ARC0610O.R89 <br />