Laserfiche WebLink
FROM TAIT & ASSOCIATES — Sac, !nto FAX NO. : 9166352606 Jan. 02 2002 11:02AM P6 <br /> Veeder Root - Leak Detection Probe Page 2 oi'2 <br /> Leak Test Performance--with 4" Floats (Third Party Certified) <br /> Probe Test Type P(D) P(FA) Test Time <br /> MAG 1 0.1 GPH 990/0 10/0 3 Hours <br /> MAG 1 0.2 990/0 <0.1% 2 Hours <br /> MAG 1 with CSLD 0.2 990/0 <0.1% Continuous <br /> Magnetostrictive Probe Console Compatibility <br /> Probe ILS-350R* TLS350fi TLS-;jQP TLS-300i TLS-300 TLS-250 TLS-250i <br /> MAG 1 ia� y/ �F v OVO <br /> r°` = Standard Feature <br /> *A Four-Input Probe Interface Module is required for use of magnetostrictive <br /> probes with the TLS-3508 or TLS-350 system. <br /> Copyright®2001 Veeder-Root, A Danaher Corporation Co <br /> contact us I a[Lvacx I Legal I email this pp I print this Daae <br /> http://www.veeder.com/dynamic/index.CfM?PagelD=105 1/2/02 <br />