Laserfiche WebLink
The Convault waste oil tank has an inspection port with"a dipstick to <br />detect leakage into the secondary containment space. <br />(5) Corrosion Protection: <br />Waste Oil Tank: <br />Protection is provided by the outer shell of 6" reinforced concrete <br />which is suitable for outdoor service without additional corrosion <br />protection. The steel tank fittings are protected be enamel paint. <br />Used Coolant Tank: <br />PVC is non-reactive with the contents of the tank and requires no <br />corrosion protection from the surrounding atmosphere. <br />Conveyance: <br />Gasoline service hose is suitable for outdoor service. <br />Galvanized pipe in protected by a non-reactive zinc coating. <br />Pumps are located inside a painted steel enclosure. <br />(6) Spill Prevention or Overfill Equipment <br />Waste Oil Tank: <br />No spill prevention or overfill equipment is installed. The adjacent <br />location of the transfer pump ensures that the operator will have <br />visual observation of the tank level. <br />Used Coolant Tank: <br />No spill prevention or overfill equipment is installed. The adjacent <br />location of the transfer pump ensures that the operator will have <br />visual observation of the tank level. <br />(7) Description of Secondary Containment: <br />Waste Oil Tank: <br />Double wall construction provides secondary containment of 1,500 <br />alg Ions which will contain 150% of the tank capacity. This meets the <br />requirement specified in 22CCR66265.1920)(1). <br />Used Coolant Tank: <br />Double wall construction provides secondary containment of 275 gallons <br />which will contain 138% of the tank capacity. This meets the requirement <br />specified in 22CCR66265.1920)(1). <br />(8) Hazardous Characteristics: <br />