Laserfiche WebLink
LEAK TEST METHOD <br />TEST ON DATE : ALL TANK <br />.JAN 29, 2009 <br />START TIME : DISABLED <br />LIQUID SENSOR SETUP <br />TEST RATE :0.20 GAL/HR <br />- - - - - - - - - - - - <br />DURATION 2 HOURS <br />L I:DISP 1-2 <br />TST EARLY STOP:DISABLED <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : DISPENSER PAN <br />L15:91 FILL SUMP <br />LEAK TEST REPORT FORMAT <br />TRI-STATE (SINGLE FLOAT) <br />NORMAL <br />CATEGORY : PIPING SUMP <br />L 2:DISP 3-4 <br />TRI-STATE (SINGLE FLOAT) <br />1_16:91 ANNULAR <br />CATEGORY : DISPENSER PAN <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : ANNULAR SPACE <br />L 3:DISP 5-6 <br />TRI-STATE (SINGLE FLOAT) <br />OUTPUT RELAY SETUP <br />CATEGORY : DISPENSER PAN <br />- - - - - - - - - - - - <br />PRESSURE LINE LEAK SETUP <br />R l:OVERFILL ALARM <br />- - - - - - - - - - - - <br />TYPE: <br />L 4:DISP 7-8 <br />STANDARD <br />TRI-STATE (SINGLE FLOAT) <br />NORMALLY OPEN <br />G 1:BLUE <br />CATEGORY : DISPENSER PAN <br />TANK #: NONE <br />TYP:2.0/3.OIN FIBERGLASS <br />2.OIN DIA LEN: 375 FEET <br />L 5:87 -SLAVE STP SUMP <br />IN -TANK ALARMS <br />3.0IN DIA LEN: 0 FEET <br />TRI-STATE (SINGLE FLOAT) <br />ALL:OVERFILL ALARM <br />CATEGORY : STP SUMP <br />ALL:HIGH PRODUCT ALARM <br />SHUTDOWN RATE: 3.0 GPH <br />ALL:MAX PRODUCT ALARM <br />LOW PRESSURE SHUTOFF:YES <br />LOW PRESSURE 5 PSI <br />L 6:87 -SLAVE FILL SUMP <br />TRI-STATE (SINGLE FLOAT) <br />T 2:BLUE MASTER <br />CATEGORY : PIPING SUMP <br />PLLD LINE DISABLE SETUP <br />DISPENSE MODE: <br />- - - - - - - - - - - - <br />STANDARD <br />SENSOR: HIGH PRESSURE <br />L 7:87 -SLAVE ANNULAR <br />G 1:BLUE <br />PRESSURE OFFSET: O.OPSI <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : ANNULAR SPACE <br />IN -TANK ALARMS <br />T 1:LEAK ALARM <br />T 2:LEAK ALARM <br />T 3:LEAK ALARM <br />L 8:87 -MASTER STP SUMP <br />T 1:LOW PRODUCT ALARM <br />TRI-STATE (SINGLE FLOAT) <br />T 2:LOW PRODUCT ALARM <br />CATEGORY : STP SUMP <br />T 3:L0W PRODUCT ALARM <br />LIQUID SENSOR ALMS <br />L 9:87 -PIASTER FILL SUMP <br />L 1:FUEL ALARM <br />TRI-STATE (SINGLE FLOAT) <br />L 2:FUEL ALARM <br />CATEGORY : PIPING SUMP <br />L 3:FUEL ALARM <br />G 2:GOLD <br />L 4:FUEL ALARM <br />L 5:FUEL ALARM <br />TYP:2.0/3.0IN FIBERGLASS <br />L10:87 -MASTER ANNULAR <br />L 8:FUEL ALARM <br />2.OIN DIA LEN: 350 FEET <br />TRI-STATE (SINGLE FLOAT) <br />Lll:FUEL ALARM <br />CATEGORY : ANNULAR SPACE <br />L 1:SENSOR OUT ALARM <br />3.OIN DIA LEN: 0 FEET <br />L 2:SENSOR OUT ALARM <br />L 3:SENSOR OUT ALARM <br />SHUTDOWN RATE: 3.0 GPH <br />L 4:SENSOR OUT ALARM <br />LOW PRESSURE SHUTOFF:YES <br />L11:87 -SIPHON STPL SUMP <br />L 5:SENSOR OUT ALARM <br />LOW PRESSURE 5 PSI <br />TRI-STATE (SINGLE FLOAT) <br />L 8:SENSOR OUT ALARM <br />CATEGORY : STP SUMP <br />Lll:SENSOR OUT ALARM <br />T 4:GOLD <br />L 1:SHORT ALARM <br />DISPENSE MODE: <br />L 2:SHORT ALARM <br />STANDARD <br />L12:87 -SIPHON FILL SUMP <br />L 3:SH0RT ALARM <br />SENSOR: HIGH PRESSURE <br />TRI-STATE (SINGLE FLOAT) <br />L 4:SHORT ALARM <br />PRESSURE OFFSET: 0.0PSI <br />CATEGORY : PIPING SUMP <br />L 5:SHORT ALARM <br />L 8:SH0RT ALARM <br />Lll:SHORT ALARM <br />1_13:87 -SIPHON ANNULAR <br />LINE LEAK LOCKOUT SETUP <br />TRI-STATE (SINGLE FLOAT) <br />ISD SITE ALARMS <br />- - - - - - - - - - - - <br />CATEGORY : ANNULAR SPACE <br />ISD GROSS FRES FAIL <br />LOCKOUT SCHEDULE <br />ISD DEGRD FRES FAIL <br />DAILY <br />ISD VAPOR LEAK FAIL <br />START TIME: DISABLED <br />TSD VP PRES FAIL <br />STOP TIME : DISABLED <br />L14:91 STP SUMP <br />TRI-STATE (SINGLE FLOAT) <br />ISD HOSE ALARMS <br />CATEGORY : STP SUMP <br />ALL:FLOW COLLECT FAIL <br />