Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for CONTI MATERIAL SVC LLC as of February 04 , 2019 . <br /> Open violations from November 29, 2018 inspection <br /> Violation #711 - Failed to perform scheduled tank tests or inspections by appropriately qualified personnel. <br /> The 10 , 000 gallon tank and the 250 gallon tanks were not tested on schedule by qualified personnel . The SPCC <br /> plan states that all tanks are to be tested per API 653 standards every 10 years. Each aboveground container shall <br /> be tested and inspected for integrity on a regular schedule and whenever repairs are made. The qualifications of <br /> personnel performing tests and inspections , frequency and type of testing and inspections that take into account <br /> container size , configuration , and design shall be determined in accordance with industry standards . Examples of <br /> these integrity tests include , but are not limited to : visual inspection , hydrostatic testing , radiographic testing , <br /> ultrasonic testing , acoustic emissions testing , or other systems of non-destructive testing . Comparison records and <br /> other records of inspections and tests must be maintained on site . Immediately conduct the necessary testing and <br /> submit a copy of the test results to the EHD , or provide equivalence as allowed by CFR 112 . 7(a)(2) , <br /> Page 1 of 1 <br />