Laserfiche WebLink
Test Date: 03/31/2003 <br /> �n�� <br /> Work Order: 2225946 <br /> SUMP TESTS SECONDARY CONTAINMENT TEST RESULTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (") (") Time Level Change Time Result Fail <br /> Dispenser Sump 19/20 Western Fiberglass Fiberglass 20" 38" Hydrostatic-VPLT 0805 14" 0.00001 0821 0.001 Pass <br /> Dispenser Sump 9/10 Western Fiberglass Fiberglass 20" 38" Hydrostatic-VPLT 0850 14" 0.00009 0906 0.001 Pass <br /> Dispenser Sump 1/2 Western Fiberglass Fiberglass 20" 38" Hydrostatic-VPLT 0935 14" 0.00003 0951 0.001 Pass <br /> Comments: <br />