Laserfiche WebLink
AUG-24-2005 12:33 Service Station Systems 408 938 eee8 P.07 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Safeway Date: 8/15105 E <br /> 1804 W.11"'St--Tracy CA 95376 i1 <br /> Test Method Developed By: Q Spill Bucket Manufacturer D Industry Standard ❑professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: M Hydrostatic u <br /> Q Othcr(Specify) <br /> Test Equipment Used:Measuring tape Equipment Resolution: <br /> Exam le_ 1/8 increments <br /> Spill Box#87 Spill Box#89 Spill Bos#91 Spill Boa# <br /> Bucket Capacity in gallons: 5-V 5-F 5-'V 5-F 5-V 5-F <br /> Bucket Depth: 12" 12" 12" 12" 12" 12" <br /> Wait time between filling with <br /> water and starting test: <br /> Test Start Time: 11:40 am 11:40 am 11:40 am 11:40 am 11:40 am 11:40 am <br /> Initial Reading(R,): 9 %" 7 7/8" 9 7/8" 1 7 /2" 7" 7 �/" <br /> Test End Time: 12:40 pm 12:40 pm 12:40 pm 12:40 pm I2.40 pm 12:40 pm <br /> Final Reading(Rp): 9V 2" 7 7/8" 97/81, 7 %" 7" 7 '44 <br /> Test Duration: 1 hour 1 hour l hour 1 hour 1 hour 1 hour <br /> I <br /> Change in Reading(RF-R,): None None None None None None <br /> Pass/Fail Threshold or Criteria: ZERO LOSS ZERO LOSS ZERO LOSS l <br /> . o :0 •'i foe.i �..P <br /> MR <br /> Comments— (include infam:ation on repairs made prior to testing, and recommended follow up.for failed tests) <br /> All Buckets Passed <br /> Tested By: Service Station Systems, Inc. Technician: Randy W. <br /> Contractor License: 485184 <br /> TOTAL P.07 <br />