h <br /> SEQUOIA ANALYTICAL <br /> 680 Chesapeake Drive • Redwood City, CA 94063 <br /> (415} 364-9600 • FAX(415) 364-9233 <br /> Blaine Tech Services, Inc Client Project ID Shell, 620 West Charter Way <br /> 985 Timothy Drive Matrix Liquid <br /> San Jose, CA 95133 <br /> Attention Jim Keller QC Sample Group 4BA1307 Reported Feb 24, 1994 <br /> QUALITY CONTROL DATA REPORT <br /> ANALYTE Benzene Toluene Ethyl Xylenes <br /> Benzene <br /> Method EPA 8020 EPA 8020 EPA 8020 EPA 8020 <br /> Analyst J Minkel J Minkel J Minkel J Minkel <br /> MS/MSD <br /> Batch# 4BA1301 4BA1301 4BA1301 4BA1301 <br /> Date Prepared - - <br /> Date Analyzed 2/18/94 2/18/94 2/18/94 2/18/94 <br /> Instrument I D # GCHP-17 GCHP-17 GCHP 17 GCHP 17 <br /> Conc Spiked 10ug/L 10u9/L long/L 30jig/L <br /> Matrix Spike <br /> % Recovery 98 98 97 100 <br /> Matrix Spike <br /> Duplicate % <br /> Recovery 100 110 110 107 <br /> Relative % <br /> Difference 2 0 12 13 68 <br /> LCS Batch# <br /> Date Prepared <br /> Date Analyzed <br /> Instrument I D # <br /> LCS % <br /> Recovery - - <br /> % Recovery <br /> Control Limits 71-133 72-128 72 130 71 120 <br /> Please Note <br /> The LCS is a control sample of known interferent free matrix that is analyzed using the same reagents <br /> . SEQUOI ANALYTICAL preparation and analytical methods employed for the samples the matrix spike is an aliquot of sample <br /> fortified with known quantities of specific compounds and subjected to the entire analytical procedure If <br /> the recovery of analytes from the matrix spike does not fall within specified control limits due to matrix <br /> interference the LCS recovery is to be used to validate the batch <br /> Suzanne Chin <br /> Project Manager 4BA1301 BLA <6> <br />