Laserfiche WebLink
% <br /> ITTS "� <br /> Integrity Tank Testis'gi Systen Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> Lj <br /> June, .22,. .19871 <br /> �I <br /> MID-CAL TRACTOR <br /> Attn : John Gilligan ! <br /> 1120 West Charter Way t <br /> Stockton, CA 95206 <br /> i <br /> I <br /> Dear Mr. Gilligan: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . 3 <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> _ 4 <br /> ,A� tank system _is considered tight, according to the ._cuxrent) a <br /> rules, if the gain is less than. 02 .or the loss - is less. than _. 05) <br /> gallons per one hour of. testing: If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 10 ,000 U/L Gaso. +. 010$4 Yes <br /> West 1.000 Diesel Fuel -. 00225 Yes <br /> Data obtained indicates the possibility of a vapor pocket. <br /> If the opportunity arises prior to your next annual test, you may <br /> wish to consider uncovering the gasoline tank and checking for <br /> items such as manways , abandoned lines , etc. Please note the <br /> enclosed sketches , <br /> We recommend --this- action only if the,�asphalt covering is to <br /> be removed for some additional purpose. ? <br /> ! <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> /V <br /> W. Savage <br /> Certified Tester <br /> } <br /> i 400 262'FEST 166 Fraak West Ciscle Stockton, CA 95206 (209) 466-8036 <br /> t <br />