�� <br /> Tait & Associates, Inc. <br /> Engineering • Architecture • Environmental <br /> PLAN CHECK RESPONSE LETTER <br /> AGENCY: City of Stockton Permit#06-303 <br /> SUBJECT: Environmental Health Comments/Building comments DATE: 08-28-06 <br /> ADDRESS: 130 S.Wilson Way <br /> Stockton,CA <br /> NO. CORRECTION REPLY SHT. <br /> ENVIRONMENTAL HEALTH. <br /> 1. Provide information that all piping,fittings,sumps and Provided this note as#5 under Compliance TI-1 <br /> under-dispensers containments is certified by an Notes <br /> independent testing organization and labeled required by <br /> the organization.(UL,ULC,ANSI,API,ASTM,etc.See <br /> title 23 Chapter 165 table B for complete list). <br /> 2. Submit a complete application for removal of pipes and <br /> dispensers. <br /> 3. Please explain the following: GC to vacuum clean drain system,see note on <br /> A. Tl-1 #10 what do you mean by"clean and flush" T1-I <br /> in that sentence? GC to convert the 91 octaine tank to 87 <br /> B. TK1-1 #35 what does reconfigure tank 2 to be 87 octaine and relable <br /> gasoline mean? <br /> C. TK3-1 Illustration 1.The ball float cannot be at Modified detail to show ball float at 90% <br /> 98% <br /> D. TK3-I Illustration 7.What is the fuel and vapor To be installed with 2"min clearance between <br /> cap height? spill container cover and dust cap,per OPW <br /> installation requirements dated May 17,2006 <br /> 4. Why are some vapor and vent lines shown as double Modified details to show as double wall tk3-3 <br /> walled and some single walled? <br /> 5. Why are you installing a new annular sensor to the tank? Existing annular sensor to be used,detail E2-3 <br /> labeled as not used <br /> 6. As per our conversation if the tank is cleaned where and Tank will not be cleaned, when 91 tank is at a <br /> how would the rinseate be disposed?Also will you be minimum level it will be refilled with 87 <br /> cutting the tank open to clean it? octane and it will be relabeled as required <br /> BUILDING COMMENTS. <br /> 1. Clearly indicate on the site plan the accessible path of Provided 5' wide path of travel,calling out as I-I <br /> travel to the city right of the way(public sidewalk)from 36"truncated domes on sidewalk ramp and at <br /> the building storefront ramp <br /> 2. Re-located ATM machine must conform to current Provided detail with ATM accessibility Al-6 <br /> accessibilities standard.Provide details accordingly. requirements <br /> 3. Showing a 60"clear space at office Al-2 <br /> Manager's office on sheet A1.2 does not appear to be <br /> accessible.The tobacco locking storage and desk appear to <br /> encroach into the space required at the door.Could a <br /> response to this item not be located on sheet A1.2 <br />